T0877 I/O Image: Detecting Collection of PLC Input and Output Tables

PDF for newsletter subscribers · free to read online

← All guides
By NHI Mgmt Group, edited by Lalit Choda Updated 12 November 2026 9 min read
On this page

I/O Image (T0877) is an adversary reading the input and output tables a PLC builds on every scan, to learn exactly what the process is doing or to record values for later replay. It is a Collection (TA0100) technique in ATT&CK for ICS, limited to embedded devices: PLCs, PACs, DCS controllers and safety controllers. ATT&CK says the technique may not be effectively mitigated, which shifts the work to detection and to the controls around the access that makes it possible. This guide explains what the I/O image is, the one documented case, the ATT&CK v20 detection analytic and how to build it, and what to do when it fires. It is for OT security engineers, control engineers and OT SOC analysts.

Key takeaways

  • The I/O image is the controller's view of the plant. The user program reads inputs from, and writes outputs to, these tables rather than touching physical I/O directly.
  • Collection is a precursor. ATT&CK notes the collected state can be used to replace values or to inform later attack stages, which is what Stuxnet did.
  • Direct mitigation is limited. ATT&CK maps only M0816 Mitigation Limited or Not Effective, so you protect the paths into the controller instead.
  • Detect the shape of the read, not its existence. Legitimate SCADA polling reads a sparse, fixed tag set; ATT&CK's analytic looks for a session reading the whole image from an unapproved source.
  • On-controller collection is hard to see. Code running inside the PLC needs no network read at all, so program integrity checks carry real weight.

What the I/O image is

ATT&CK for ICS describes it as follows. During the scan cycle a PLC reads the status of all inputs and stores them in an image table, the controller's internal storage for the input and output values of one scan while it runs the user program. After the logic has been solved, the PLC updates the output image table, and its contents are written to the output points on the I/O modules. Together the input and output image tables make up the I/O image. Adversaries may collect it by using the device's Native API (T0834) to access those memory regions directly.

Access pathHow the image could be readWhere it is visible
Network protocol session from a hostReading the I/O address range over the controller's industrial protocolOT network monitoring with protocol decoding
Code running on the controllerMalicious logic copying image areas into data blocksProgram and block integrity comparison against the approved project
Engineering software on a compromised hostOnline monitoring or diagnostic views of I/O valuesEngineering workstation logs; session source in network monitoring

For the controller fundamentals behind this, see the PLC Security Guide. This page focuses on the technique itself.

The documented case: Stuxnet

T0877 has one procedure example in ATT&CK v20. ATT&CK records that Stuxnet (S0603) copied the input area of an I/O image into data blocks with a one second interval between copies, forming a 21 second recording of the input area, such as the current state of a valve or the temperature of a device. The Symantec W32.Stuxnet Dossier describes a monitoring routine that recorded values from frames sent by frequency converter drives over Profibus, and later attack stages that sent frames which partly depended on what had been recorded.

Lesson: collection was done by code inside the controller, so a network read detector would not have seen it. Stuxnet also hid its blocks from the engineering software through a hooked library (see ATT&CK for ICS T0874 Hooking). Program integrity must be verified from a trusted path. No other public procedure examples are listed by ATT&CK for this technique.

Detection: the ATT&CK v20 analytic

The detection strategy for T0877 (DET0774, Detection of I/O Image) has one analytic, AN1906, for embedded devices. It identifies a single ICS protocol session reading the complete I/O image from a field device, rather than the sparse, fixed tag subset that legitimate SCADA polling queries, from a source that is not in the approved control server list. ATT&CK's operational fidelity gate applies: do not alert on novelty, read volume or enumeration alone; alert when the source role is not authorised for polling and the target scope, address or tag range, protocol or rate departs from the baseline; suppress normal SCADA, HMI and historian polling, commissioning, asset inventory, backup, diagnostics and approved engineering work.

Building it

  1. Inventory the legitimate readers. For each controller, list the SCADA servers, HMIs, historians and engineering stations that poll it, and which address or tag ranges each reads. Your OT monitoring platform's communication map is the starting point; see the OT Asset Visibility Guide.
  2. Know each controller's I/O size. The analytic's coverage threshold is a percentage of the device's total I/O space, so you need that size per controller from the project files.
  3. Decode the protocol. Coverage depends on the monitoring sensor parsing read requests and address ranges for the protocols in use; check which of your controller protocols it decodes fully.
  4. Set the threshold with engineers. Choose a coverage percentage that normal polling never reaches, and list the sources that may legitimately exceed it (backup and commissioning tools).
  5. Run in observation mode first. Compare alerts with the maintenance calendar for several weeks before paging anyone.
SignalLikely benignWorth investigating
Full-range read from the engineering station during a scheduled changeYes, if a change ticket matchesIf no ticket exists or it occurs outside the window
Full-range read from a historian or SCADA serverRarely, usually a configuration changeYes, confirm with the system owner
Any read from a host outside the approved listAsset inventory or diagnostic tool if documentedYes, especially from IT-side or remote access subnets
Repeated reads of the same input area at fixed intervalsTrending configured by engineersYes, if the source is new or the pattern is new

Network detection covers only the first path. For code inside the controller, rely on comparing the running program with the approved project, from a trusted host, after every download and on a schedule. See the OT Network Security Monitoring Guide for sensor placement.

Prevention: controlling the paths in

Because ATT&CK maps only M0816 to T0877, prevention means narrowing who and what can reach controller memory:

  • Restrict protocol access to controllers: allow controller protocols only from named SCADA servers, HMIs and engineering stations, and block them at every other conduit. See the OT Network Segmentation, Purdue Model and IEC 62443 Zones and Conduits Guide.
  • Use controller access protections: where the product supports read and write protection levels or passwords on online access, turn them on and replace defaults.
  • Protect the engineering station: it can read everything the controller holds. See the Engineering Workstation Security Guide.
  • Verify program integrity: on-controller collection needs modified logic, so integrity checks after downloads close the second path.
FrameworkReferenceRelevance to T0877
ATT&CK for ICSM0816 Mitigation Limited or Not EffectiveSignals that controls must target the access paths
NIST SP 800-53 Rev. 5SC-7 Boundary ProtectionLimits which hosts can reach controller protocols
NIST SP 800-53 Rev. 5SI-4 System MonitoringProtocol-aware monitoring of read scope
NIST SP 800-53 Rev. 5SI-7 Software, Firmware, and Information IntegrityDetects logic added to copy image areas
NIST CSF 2.0DE.CM-09, DE.AE-02Monitoring and analysis of adverse events on OT assets

Where identity fits

Most legitimate I/O reads come from service accounts and applications: SCADA servers, historians and their collectors. Treat the approved reader list as an identity inventory for machines, and review vendor and integrator remote access that can reach controllers. See the OT and ICS Identity and Access Guide.

When the analytic fires

  1. Identify the source host and its owner, then check for a matching change ticket or maintenance activity.
  2. Do not disrupt the controller. A read does not change the process; avoid restarts or mode changes as a first reaction.
  3. Contain the source, for example by blocking it at the conduit firewall, after agreeing with operations that it is not a needed HMI or SCADA server.
  4. Look for the next stage: program downloads, parameter writes or mode changes to the same controller, since collection informs later steps.
  5. Verify the controller program against the approved project from a trusted host. See the OT Incident Response Guide.

Measuring coverage

  • Reader inventory: share of controllers with a documented list of approved reading hosts and address ranges.
  • Protocol decode coverage: share of controller protocols in use that your sensors parse down to address ranges.
  • Integrity check cadence: share of controllers whose program was compared with the approved project in the last period you set.
  • Conduit enforcement: number of hosts outside the approved list that can reach controller protocol ports, which should trend to zero.

Common failure patterns

  • Alerting on any new reader: ATT&CK advises against novelty-only alerts; commissioning and inventory tools will flood the queue.
  • Relying on the network alone: Stuxnet's collection ran inside the controller and would not appear as a network read.
  • No per-controller I/O size: without it, the coverage threshold cannot be set and the analytic is guesswork.
  • Flat access to controllers: when any host in the control network can talk to any PLC, the approved list has no meaning.

Practitioner checklist

  • Document the approved reading hosts and address ranges for each controller.
  • Record each controller's total I/O space from the project files.
  • Confirm your OT sensors decode read requests and address ranges for each protocol in use.
  • Implement AN1906 in observation mode, then tune with control engineers.
  • Restrict controller protocol access at conduits to the approved hosts.
  • Turn on controller access protection where the product supports it.
  • Compare running programs with approved projects after every download and on a schedule.

Standards and references

Related NHI Mgmt Group resources: PLC Security Guide, ATT&CK for ICS Impair Process Control Tactic Guide, ICS Malware History Guide, OT Security Guide.

PDF for subscribers

Take this guide with you

Every section, table and checklist in one PDF, with links to the sources and related guides. Subscribe to our weekly NHI & AI Identity Journal and we’ll email you a download link.

Free weekly newsletter

Subscribe to the NHI & AI Identity Journal

The latest on NHI and Agentic AI security – articles, research, breaches, news and events every week.

Bonus 33% off our NHI Course when you subscribe.

NHIMG Editorial Note
Researched and written by the NHI Mgmt Group editorial team using AI tools, under the editorial direction of Lalit Choda. Facts are drawn from the sources listed on this page and checked by our automated quality process. Last updated 12 November 2026. Spotted an error? Use our contact page.
NHI Mgmt Group, the independent authority on Non-Human Identity, IAM and Agentic AI security. nhimg.org

PDF Downloads for Newsletter Subscribers

Get the guide

Enter your details and we’ll email you a download link.

The full guide is free to read online. The PDF is a thank you for subscribing.

Fill in all fields marked * and tick the PDF box to continue.