NERC CIP-015 is the first North American reliability standard that requires electric utilities to watch the traffic inside their protected networks, not just at the perimeter, so that an intruder who has already got in is more likely to be noticed. CIP-015-1 covers networks inside the Electronic Security Perimeter of high impact BES Cyber Systems and medium impact BES Cyber Systems with External Routable Connectivity. CIP-015-2, developed in response to FERC Order No. 907, extends internal network security monitoring (INSM) to access control and monitoring systems and physical access control systems that can sit outside that perimeter. This guide sets out what each version requires, who is in scope, the compliance timeline, and a practical build plan for the sensors, detections and evidence an audit will expect. It narrows in on CIP-015; for the full CIP family see the NERC CIP Guide, and for the monitoring technology itself see the OT Network Security Monitoring Guide.

This page is general information, not legal advice. Status as of 17 Nov 2026. Confirm dates and requirement text against the NERC standard, the implementation plan and FERC's orders before relying on them.

Key takeaways

  • CIP-015-1 has three requirements: implement INSM processes (R1, with Parts 1.1 to 1.3), retain data on anomalous activity until the follow-up action is complete (R2), and protect INSM data from unauthorised deletion or modification (R3).
  • FERC approved CIP-015-1 in Order No. 907, published in the Federal Register on 2 July 2025 and effective 2 September 2025. The same order directed NERC to extend INSM to EACMS and PACS outside the Electronic Security Perimeter.
  • Under NERC's implementation plan, CIP-015-1 takes effect on the first day of the first calendar quarter 36 months after the approving order's effective date. Control Centres and backup Control Centres must comply on that date; other medium impact BES Cyber Systems with ERC have a further 24 months.
  • CIP-015-2 was adopted by the NERC Board on 17 June 2026 and filed with FERC on 1 July 2026; check FERC eLibrary for whether an approving order has since been issued. It moves scope from "networks protected by the ESP" to network activity between Cyber Systems in a table of applicable systems that includes EACMS, PACS, PCA and Shared Cyber Infrastructure.
  • The standard is technology neutral. It asks for a documented, risk-based rationale for data feeds, a method to detect anomalies and a method to evaluate them, not for a particular product.

CIP-015 at a glance

ItemCIP-015-1CIP-015-2 (filed with FERC)
Purpose"To improve the probability of detecting anomalous or unauthorized network activity in order to facilitate improved response and recovery from an attack."Same purpose, wider scope.
OriginFERC Order No. 887 directiveFERC Order No. 907 directive
Monitoring scopeNetworks protected by the ESP of high impact BCS and medium impact BCS with ERCNetwork activity between Cyber Systems in Table R1: BCS, EACMS, PACS and PCA associated with high impact and medium impact with ERC, plus supporting Shared Cyber Infrastructure
RequirementsR1 (Parts 1.1 to 1.3), R2, R3Parts 1.1 to 1.3 keep the same language according to NERC's technical rationale
StatusFERC approved, Order No. 907 (Docket RM24-7-000)Board adopted 17 June 2026; petition filed with FERC 1 July 2026; check FERC eLibrary for the approving order

Scope

Responsible entities and facilities

CIP-015-1 applies to Balancing Authorities, Distribution Providers (for specified facilities only), Generator Operators, Generator Owners, Reliability Coordinators, Transmission Operators and Transmission Owners. For Distribution Providers the facilities are limited to specified UFLS and UVLS systems, Remedial Action Schemes, certain Transmission Protection Systems and Cranking Paths. For the other entities the facility applicability is all BES Facilities.

Exemptions

The standard exempts, among other things, Cyber Systems at facilities regulated by the Canadian Nuclear Safety Commission, certain communication links between discrete ESPs and between locations, systems regulated by the US Nuclear Regulatory Commission under 10 CFR 73.54, and Responsible Entities with no high impact or medium impact BES Cyber Systems with External Routable Connectivity. Low impact assets are therefore outside CIP-015 entirely; their obligations sit in CIP-003.

Which networks

The key scoping line for CIP-015-1 is in R1 itself: networks protected by the Responsible Entity's Electronic Security Perimeters of high impact BES Cyber Systems and medium impact BES Cyber Systems with ERC. That depends on accurate categorisation under CIP-002, so treat your CIP-002 inventory as the starting point. The NERC CIP-002 BES Cyber System Categorisation Guide covers that step.

CIP-015-2 changes the question. NERC's technical rationale explains that scope becomes network activity between Cyber Systems that are part of the applicable systems in Table R1. Those include EACMS, PACS and Protected Cyber Assets associated with in-scope BES Cyber Systems, plus the Shared Cyber Infrastructure that supports them. EACMS and PACS can sit outside the ESP, which is the gap FERC identified. Traffic to or from non-CIP devices, low impact BCS and activity between discrete ESPs stay out of scope.

Key obligations

R1: internal network security monitoring processes

Each Responsible Entity must implement one or more documented processes for INSM that include three parts:

  • Part 1.1: implement, using a risk-based rationale, network data feeds to monitor network activity, including connections, devices and network communications.
  • Part 1.2: implement one or more methods to detect anomalous network activity using those data feeds.
  • Part 1.3: implement one or more methods to evaluate anomalous network activity detected under Part 1.2 to determine further actions.

R1 carries a Medium Violation Risk Factor with time horizons of Same Day Operations and Operations Assessment.

R2: retain data on anomalies

Except during CIP Exceptional Circumstances, entities must implement documented processes to retain INSM data associated with network activity they have determined to be anomalous, at a minimum until the action is complete, in support of Part 1.3. R2 has a Lower Violation Risk Factor.

R3: protect INSM data

Except during CIP Exceptional Circumstances, entities must implement documented processes to protect INSM data to mitigate the risks of unauthorised deletion or modification. R3 also has a Lower Violation Risk Factor.

What the measures expect as evidence

The measures describe evidence such as a risk-based rationale for data feeds, detection event records and baselines, evaluation methods, response actions and escalation processes (which may include CIP-008 incident response plans), retention configurations or reports showing timelines sufficient to support Part 1.3, and documentation showing how monitoring data is protected.

Timeline and implementation

FERC approved CIP-015-1 on 26 June 2025 in Order No. 907. The final rule was published on 2 July 2025 and became effective on 2 September 2025. Order No. 907-A, issued on 21 August 2025, clarified the term "CIP-networked environment". FERC gave NERC 12 months from the final rule's effective date to file the extension to EACMS and PACS.

NERC's implementation plan for CIP-015-1 says the standard becomes effective on the first day of the first calendar quarter that is 36 months after the effective date of the approving governmental order. Applying that formula to the 2 September 2025 effective date gives a US effective date of 1 October 2028 (our own calculation, not a date published by NERC or FERC). Control Centres and backup Control Centres must comply on the effective date. Medium impact BES Cyber Systems with ERC other than Control Centres must comply within 24 calendar months after it. The plan notes that some generating plants may need scheduled outages or upgrades before sensors can be installed, which is a strong reason to plan early.

For CIP-015-2, the IESO summary records NERC Board adoption on 17 June 2026 and a petition to FERC on 1 July 2026. Implementation dates for CIP-015-2 depend on its approving order and implementation plan, so confirm them in FERC eLibrary and on NERC's project page before fixing a programme schedule. Canadian jurisdictions run their own approval processes; for example, the IESO posted the standard for Ontario Energy Board review, with the review period ending on 31 October 2026.

Enforcement and penalties

CIP-015 is enforced in the same way as the rest of the CIP family: Regional Entities audit and monitor compliance, and NERC files penalties with FERC. Each requirement's Violation Risk Factor (Medium for R1, Lower for R2 and R3) and the Violation Severity Level found feed into the penalty determination under NERC's sanction guidelines. In practice, the bigger risk is an audit finding that INSM exists on paper but cannot show feeds, detections, evaluations and protected retention for each in-scope network. Track the published Compliance Monitoring and Enforcement details for CIP-015 through your Regional Entity.

What it means for security and identity teams

INSM is about lateral movement: an attacker who has stolen a vendor remote access account, or compromised an engineering workstation, and is now moving between systems inside the perimeter. That makes identity central to good detections.

  • Remote access paths. Watch for use of remote services between assets that do not normally talk, mapped in ATT&CK for ICS as T0886 Remote Services, and for scanning or enumeration mapped as T0846 Remote System Discovery.
  • Service and application accounts. Historians, SCADA servers and backup tools authenticate to many devices with shared or service credentials. Baseline which machine identities connect where, and treat a new source using a known service account as anomalous.
  • EACMS under CIP-015-2. Intermediate systems, jump hosts, authentication servers and log collectors are EACMS. Once CIP-015-2 applies, traffic between them and other applicable systems must be monitored, which catches abuse of the very systems that grant access.
  • PACS under CIP-015-2. Badge controllers and their servers are often managed by facilities teams. NERC's technical rationale says traffic between a PACS controller and other applicable Cyber Systems, including the PACS server, must be captured at some point.

Map INSM into the wider monitoring control set: NIST SP 800-53 SI-4 System Monitoring describes the same goal, and AU-9 Protection of Audit Information mirrors R3. The OT and ICS Identity and Access Guide covers the access controls these detections watch over.

Compliance steps

  1. Confirm scope. Start from the CIP-002 list of high impact and medium impact with ERC BES Cyber Systems. For each ESP, list the networks, VLANs and virtual switches. For CIP-015-2 readiness, add every EACMS, PACS, PCA and Shared Cyber Infrastructure component tied to those systems, including those outside the ESP.
  2. Write the risk-based rationale. NERC's technical rationale describes a data feed as a collection location (such as a core switch, VLAN or virtual switch) combined with a collection method. Record for each network which feeds you chose, which you excluded and why, using adversary technique analysis, impact analysis and protocol coverage as the basis.
  3. Choose collection methods. NERC lists TAPs, mirror or SPAN ports, flow data (NetFlow, sFlow, IPFIX), RSPAN, sensors, software defined networking, firewall "bump in the wire" and endpoint agents. Prefer passive collection in substations and plants, and check that sensors understand the industrial protocols in use.
  4. Build detections. The standard does not mandate a baseline or a technology. Signature, behavioural, indicator, configuration checking and anomaly methods are all acceptable. Most utilities combine a communications baseline with signatures and identity based rules, documented as the Part 1.2 method.
  5. Define evaluation. Part 1.3 requires a method to evaluate anomalies and decide further action. Write triage playbooks, assign owners, and set out the hand-off to CIP-008 incident response when an anomaly becomes a suspected Cyber Security Incident.
  6. Retain and protect data. Configure retention so data tied to an anomaly is kept until the action is complete (R2), and store it where operators of monitored systems cannot delete or modify it, with access logging and integrity controls (R3).
  7. Generate evidence continuously. Keep dated records of feeds, detection events, evaluations and retention settings. Rehearse an audit sample before your Regional Entity asks for one.
  8. Plan outages and change control. Sensor installation in generating plants and substations may need scheduled outages. Put them in the maintenance calendar now, given the phased dates.

For the sensor, toolchain and baselining detail behind steps 3 and 4, the Zeek Network Monitoring Guide and the OT Network Security Monitoring Guide go further.

Common failure patterns

  • A rationale that lists sensors but never explains why other networks or segments were excluded.
  • Monitoring only north to south traffic at the ESP boundary, which is perimeter monitoring, not INSM.
  • Detections that alert but no documented Part 1.3 evaluation, so anomalies are closed without a recorded decision.
  • Retention that ages out data on a fixed schedule before the related investigation is finished.
  • INSM data stored on systems the monitored administrators can alter, failing R3.
  • Ignoring virtual switches and hypervisor traffic, where much ESP traffic now runs.
  • Treating CIP-015-2 as a later problem, then finding EACMS and PACS outside the ESP have no collection points.
  • Sensor projects in plants delayed because outage windows were not booked in time.

Practitioner checklist

  • Every high impact and medium impact with ERC ESP has a documented list of networks and data feeds.
  • A written risk-based rationale covers selected and excluded feeds for each network.
  • Detection methods are documented, tuned and producing dated event records.
  • An evaluation process with owners, triage steps and CIP-008 escalation exists and is used.
  • Retention keeps anomaly data until actions complete and is configured, not assumed.
  • INSM data is protected against deletion and modification, with separate administration.
  • An inventory of EACMS, PACS, PCA and Shared Cyber Infrastructure is ready for CIP-015-2.
  • Compliance dates for each site type are in the programme plan, with outage windows booked.
  • Detections cover remote access and service account behaviour between assets.

Standards and references

Related NHI Mgmt Group resources: NERC CIP Guide · NERC CIP-013 · OT Network Security Monitoring Guide · Zeek Network Monitoring Guide

PDF for subscribers

Take this guide with you

Every section, table and checklist in one PDF, with links to the sources and related guides. Subscribe to our weekly NHI & AI Identity Journal and we’ll email you a download link.

Free weekly newsletter

Subscribe to the NHI & AI Identity Journal

The latest on NHI and Agentic AI security – articles, research, breaches, news and events every week.