Operational technology security needs its own metrics because the things that matter in a plant (safe operation, uptime, the ability to restore a controller) are not what an IT security dashboard measures. Patch rates, phishing click rates and mean time to detect are useful in the office, but they say little about whether an engineer can see every PLC on a line, whether a remote access path into a substation is still open, or whether the site could rebuild its control logic after a ransomware event.
This guide sets out a practical OT metric set organised around three questions: how much of the environment can we see, how exposed is it, and how quickly can we recover. It explains how to collect the data without disturbing operations, how to set targets that plant managers accept, and how to report to executives and boards. It assumes a general measurement programme already exists; the Security Metrics and KPIs Programme Guide covers metric types and governance, and the OT Security Maturity Model covers capability levels.
Key takeaways
- Organise OT metrics around visibility, exposure and recovery. Those three themes map directly to what attackers exploit and what operators fear.
- Count assets by site, zone and criticality, not as a single total. A 95 per cent inventory figure can hide a completely unknown safety system.
- Measure exposure through paths, not just vulnerabilities: internet-facing devices, remote access routes, IT to OT conduits and shared credentials.
- Patch metrics need an OT definition. Many assets cannot be patched quickly, so measure whether each known vulnerability is patched, mitigated by a compensating control, or accepted with a named owner.
- Recovery metrics should be tested, not declared. Backup coverage of controller logic and the date of the last successful restore test are more telling than backup job success rates.
- CISA's Cross-Sector Cybersecurity Performance Goals give OT-specific, measurable baselines, such as asset inventories updated at least monthly, that work well as starting targets.
Why OT needs different metrics
NIST SP 800-82 Rev. 3, the Guide to Operational Technology (OT) Security, describes OT as programmable systems and devices that monitor or control physical processes, and stresses that OT has unique performance, reliability and safety requirements. Those requirements change what good looks like.
- Availability outranks speed of change. A fast patch cycle is a good IT metric; in OT, an untested patch that trips a line is a safety and production incident.
- Assets live for decades. Controllers and HMIs may run unsupported operating systems for years. Metrics must handle long-lived risk honestly rather than showing permanent red.
- Collection must be passive. Active scanning can disrupt fragile devices. Metric data usually comes from passive network monitoring, engineering workstation records and configuration management, not agents.
- Ownership is shared. Engineering, operations, maintenance contractors and IT all touch OT systems. Each metric needs an owner who can act on it.
The NIST Cybersecurity Framework 2.0 expects organisations to evaluate and review risk management performance (GV.OV-03). In OT, that evaluation must be meaningful to plant managers as well as security teams, so metrics should be expressed in terms of sites, lines and processes.
A metric framework: visibility, exposure, recovery
NIST SP 800-55 Vol. 1, the Measurement Guide for Information Security published in December 2024, helps organisations develop measures that show whether security policies, procedures and controls are adequate. Applied to OT, a compact framework covers three themes, plus a small set of governance measures.
| Theme | Core question | Example measures |
|---|---|---|
| Visibility | Can we see and describe what we run? | Inventory coverage, monitoring coverage, configuration baselines |
| Exposure | How could an attacker get in or move? | Internet-exposed assets, remote access paths, conduit compliance, vulnerability status |
| Recovery | Could we restore safe operation? | Logic backup coverage, restore test age, incident exercise frequency |
| Governance | Is the programme working? | Named site owners, OT training completion, exception age |
Keep the headline set small, around 10 to 15 measures, and let each site drill into detail. A board does not need 80 OT metrics; it needs to know which sites are below baseline and what is being done.
Visibility metrics
You cannot protect what you cannot see. CSF 2.0 expects inventories of hardware to be maintained (ID.AM-01), and CISA's CPGs set a measurable baseline: asset inventories for IT and OT updated at least monthly.
| Metric | Definition | Why it matters |
|---|---|---|
| Inventory coverage by zone | Assets discovered by passive monitoring that are in the asset register, divided by total assets discovered, per site and zone | Shows unknown devices where they are, not averaged away |
| Inventory freshness | Share of sites whose OT inventory was reconciled in the last 30 days | Tracks the CPG monthly baseline directly |
| Critical asset completeness | Share of safety and critical control assets with firmware version, owner and network location recorded | Vulnerability and recovery work depends on these fields |
| Monitoring coverage | Share of OT network segments with passive network monitoring feeding the security operations team | Detection is impossible on unmonitored segments |
| Configuration baseline coverage | Share of controllers with a stored known good logic and configuration baseline | Needed to detect unauthorised change and to recover |
The OT Asset Visibility Guide explains how passive discovery works and how to reconcile it with engineering records.
Exposure metrics
Exposure metrics measure the paths an attacker could use. They are usually more actionable than raw vulnerability counts.
Connectivity and access
- Internet-exposed OT assets. Count of OT devices reachable from the internet, from external attack surface data and firewall review. CISA's CPGs include a goal to limit OT connections to the public internet, so the target is usually zero without a documented business need.
- Remote access paths. Number of distinct remote access routes into OT, and the share that go through an approved, monitored gateway with multi-factor authentication. Unapproved vendor modems and direct VPNs are the usual findings.
- Conduit compliance. Share of IT to OT and zone to zone flows that match the approved conduit rules. CISA's CPGs include network segmentation between IT and OT as an OT-specific goal.
- Shared and default credentials. Count of OT accounts or devices using shared, default or vendor-supplied passwords, by site.
- Physical port control. Share of critical OT assets with unused physical ports disabled or controlled, matching the CPG goal on physical ports.
Vulnerability status
For OT, a simple "patched within X days" metric is misleading. CISA's CPGs explicitly include compensating controls for OT assets that cannot be patched. A better metric tracks every known vulnerability on a critical OT asset into one of four states.
| State | Meaning |
|---|---|
| Patched | Vendor fix installed and validated |
| Mitigated | A documented compensating control is in place, such as segmentation, disabled service or access restriction |
| Accepted | Risk accepted by a named owner with a review date |
| Open | No decision yet |
Report the share in "Open" and the age of the oldest open item, with special attention to vulnerabilities listed in CISA's Known Exploited Vulnerabilities catalogue. The OT Patch Management Guide covers the testing and maintenance window process behind these numbers, and the Vulnerability Management Metrics guide covers general vulnerability measurement.
Detection and response metrics
OT detection metrics should show whether the security operations team can see and act on OT events, and whether operations staff are part of the process.
- OT alert triage time. Median time from an OT alert to a triage decision, measured separately from IT alerts.
- Engineering change correlation. Share of detected controller logic or configuration changes that match an approved change record. Unmatched changes are either process gaps or incidents.
- Use case coverage. Number of OT-specific detection use cases in production, such as new remote session to a controller, firmware download, mode change or unexpected protocol use.
- Joint exercise frequency. Date of the last tabletop or live exercise involving security, operations and engineering. CISA's CPGs call for incident response plans to be drilled at least annually.
The OT Incident Response Guide covers the response process these metrics measure, and the Incident Response Metrics and KPIs Guide covers general response measures.
Recovery metrics
Recovery is where OT metrics most often flatter. A backup job that "succeeds" every night may be backing up the wrong files, or a version of controller logic that is months out of date. CISA's CPGs include an OT-specific goal for backups covering items such as PLC logic, and CSF 2.0 expects backup integrity to be verified before use in restoration (RC.RP-03).
| Metric | Definition |
|---|---|
| Logic backup coverage | Share of critical controllers with a current backup of logic and configuration that matches the running version |
| Restore test age | Days since a successful test restore of a representative controller, HMI and engineering workstation per site |
| Offline copy coverage | Share of critical backups held offline or immutably, out of reach of IT network ransomware |
| Documented recovery time | Time to restore a line to safe manual or automated operation, measured in the last exercise |
| Spares and media readiness | Share of critical asset types with tested spare hardware and installation media available |
The OT Backup, Recovery and Golden Image Guide describes how to build the backups these metrics test.
Governance and people metrics
- Site ownership. Share of sites with a named OT security lead. CISA's CPGs include OT cybersecurity leadership as a goal.
- OT training completion. Share of engineers, operators and OT contractors who completed OT-specific training in the last 12 months. CPGs include OT-specific training as a goal.
- Exception age. Count and median age of open security exceptions, such as unsupported systems or unapproved remote access.
- Supplier assurance. Share of critical OT suppliers and integrators with security requirements in contract and a current assessment.
Collecting OT metric data safely
The quality of an OT metric depends on where its data comes from, and the wrong collection method can itself become a risk to operations. Agree the sources for each measure with site engineering before the first report.
- Passive network monitoring is the main source for inventory, monitoring coverage, conduit compliance and unexpected protocol use. It observes traffic from span ports or taps without sending packets to devices.
- Engineering and configuration records supply firmware versions, logic versions and backup status. Where engineering workstations hold project files, compare them with what passive monitoring sees running.
- Change management systems provide the approved change records needed to correlate logic and configuration changes.
- Remote access gateway logs show approved sessions, which can be compared with flows that bypass the gateway.
- Exercise and restore test records provide recovery evidence. Keep the dated results, not just a statement that a test occurred.
Where an active query is unavoidable, use vendor-supported methods during agreed maintenance windows, and record that the data point was collected that way. Automate collection where possible: manually compiled spreadsheets drift and invite disputes about whose numbers are right.
Setting targets and reporting
Targets in OT must be agreed with operations. A target imposed by IT will be resisted, or met on paper only.
- Baseline first. Measure for one or two quarters before setting targets. Many sites will find their first honest inventory coverage figure far below expectations.
- Use the CPGs as a floor. CISA describes the CPGs as a voluntary, prioritised subset of practices that larger organisations can use as a baseline for measuring maturity. They make good initial targets because regulators and insurers recognise them.
- Tier by criticality. Set tighter targets for safety and critical process zones than for building management or office-adjacent zones.
- Report trends by site. Show executives which sites are improving, which are flat and which are below baseline, with the top three actions for each.
- Pair every red metric with a plan. A red figure without an owner and a date becomes background noise.
Define each measure in a dictionary so that every site counts the same way. The Security Metrics Dictionary Template provides a format, and KRI vs KPI in Cyber Security explains when a measure is a risk indicator rather than a performance indicator.
Common failure patterns
- One fleet-wide number. A single inventory or patch percentage hides the site or zone where the real risk sits.
- Importing IT patch SLAs. OT teams are judged against 30-day patch targets they cannot safely meet, and stop engaging with the metrics.
- Counting backups, not restores. Backup success rates look perfect until a real restore fails.
- Active scanning for metrics. Data collection disturbs fragile devices and turns operations against the security programme.
- No owner per metric. Numbers are reported but nobody at the site is responsible for moving them.
- Remote access blind spots. Vendor connections outside the approved gateway are never counted, so exposure looks lower than it is.
- Too many measures. A dashboard with dozens of OT metrics overwhelms executives and hides the few that matter.
Practitioner checklist
- Agree three headline themes, visibility, exposure and recovery, with operations and engineering leads.
- Select 10 to 15 headline measures and define each in a metrics dictionary.
- Collect data passively from network monitoring, configuration management and change records.
- Report inventory coverage by site and zone, with critical assets tracked separately.
- Count internet-exposed OT assets and remote access paths, aiming for zero unapproved paths.
- Track every known vulnerability on critical assets as patched, mitigated, accepted or open.
- Measure logic backup coverage and the age of the last successful restore test per site.
- Use CISA CPG OT goals as baseline targets and tier them by zone criticality.
- Give every metric an owner and pair every red result with a dated action.
- Review the metric set yearly against SP 800-82 updates and incident lessons.
Standards and references
- NIST: SP 800-82 Rev. 3, Guide to Operational Technology (OT) Security
- NIST: SP 800-55 Vol. 1, Measurement Guide for Information Security
- CISA: Cross-Sector Cybersecurity Performance Goals
- NIST: Cybersecurity Framework 2.0
- NIST: SP 800-61 Rev. 3, Incident Response Recommendations and Considerations for Cybersecurity Risk Management
- CISA: Secure by Design
Related NHI Mgmt Group resources: OT Security Maturity Model · Security Operations Metrics Guide · NIST SP 800-82 OT Security Guide · OT Security Programme Health Check