Most industrial operators can list the OT security tools they have bought, but few can show whether a vendor could still reach a controller tonight with a shared password, or whether the plant could run for a week with IT switched off. OT maturity is whether controls hold at the site with the oldest equipment, the most remote access and the thinnest staff. This model scores OT security on the same five-level Ad hoc to Optimised scale as the other NHI Mgmt Group maturity models, across ten capability domains, and lines those levels up with the US DOE C2M2, IEC 62443, CISA's Cross-Sector Cybersecurity Performance Goals (CPGs) and the NCSC Cyber Assessment Framework (CAF). It is for OT security leads, plant and engineering managers and CISOs who need an honest baseline across sites. For OT fundamentals, see the OT Security Guide.
Key takeaways
- Score each site and each domain separately. A corporate average hides the one plant with an internet-exposed PLC, and that plant sets your real level.
- Maturity and security level are different measures. IEC 62443 security levels describe the attacker a zone can withstand; maturity levels describe how reliably the processes that keep it there are run.
- Level 3 (Defined) is the right first target: a passive inventory, documented zones and conduits, brokered remote access with named accounts, and an OT incident plan exercised with operators.
- Identity is the domain most sites score lowest on. Default and shared credentials, always-on vendor access and old service accounts on historians and engineering workstations are common ways in.
- Score evidence, not policy: inventory exports, dated rule reviews, remote session records, restored logic backups and manual operation drills.
The five levels
| Level | Name | Description |
|---|---|---|
| 1 | Ad hoc | Security depends on individual engineers. No reliable inventory, flat or dual-homed networks, vendors connect with shared or default credentials, and nobody owns OT cyber risk. |
| 2 | Developing | An OT security owner is named and initial practices are performed unevenly across sites: partial inventory, an IT/OT firewall without reviewed rules, a remote access tool not always used. |
| 3 | Defined | Documented, resourced practices at every site: passive inventory, zones and conduits with an industrial DMZ, brokered remote access with MFA and recording, an OT incident plan and offline logic backups. |
| 4 | Managed | Practices are measured and enforced: target security levels per zone, scheduled rule and account reviews, OT detections handled by the SOC, supplier terms in contracts, and timed recovery drills. |
| 5 | Optimised | Metrics, incidents and threat intelligence drive improvement. Consequence-based engineering removes cyber-exploitable failure modes from the worst scenarios, and security capability rises at every refresh. |
How the levels relate to C2M2, IEC 62443, CPGs and the CAF
This model gives one scale to compare sites; keep the framework your regulator or customers ask for as the system of record.
| Framework | What it measures | Scale | Best used for |
|---|---|---|---|
| US DOE C2M2 Version 2.1 (June 2022) | 356 practices in 10 domains, IT and OT | MIL1 Initiated, MIL2 Performed, MIL3 Managed (MIL0: not performed) | Energy and critical infrastructure self-evaluation with per-domain targets |
| ISA/IEC 62443 maturity levels (2-1:2024, 2-4, 4-1) | How well asset owners, service providers and suppliers run security processes | ML1 Initial, ML2 Managed, ML3 Defined (Practiced), ML4 Improving | Holding integrators and suppliers to a stated maturity per requirement |
| ISA/IEC 62443 security levels (3-3, 4-2) | Strength of technical requirements per zone, system or component | SL 1 to SL 4, as target (SL-T), capability (SL-C) and achieved (SL-A) | Design and procurement |
| CISA Cross-Sector CPGs | 38 baseline goals for IT and OT, organised by CSF functions | Goal met or not met | A minimum baseline for small operators |
| NCSC CAF 4.0 | Outcomes and indicators of good practice across four objectives and 14 principles | Not achieved, Partially achieved or Achieved, against a CAF Profile | UK operators of essential services under the NIS Regulations |
Approximate correspondence: Level 2 here is close to C2M2 MIL1 and 62443 ML1 (performed but ad hoc); Level 3 to MIL2 and ML2 to ML3 (documented, resourced, followed); Level 4 to MIL3 (policy-driven, responsibility assigned, effectiveness tracked); Level 5 to ML4, where process metrics drive improvement. Treat this as a sense check, not an equivalence.
The 62443 maturity level names come from the ISA Global Cybersecurity Alliance quick start guide, which notes that ML4 combines CMMI levels 4 and 5 and that "Security Levels are a measure of the strength of technical requirements, Maturity Levels are a measure of processes." The standard texts are paywalled; the public 2-4:2023 preview lists a maturity model clause but not the definitions. See the IEC 62443 Guide for zones, conduits and security levels.
Choosing a frame: US energy operators usually start with C2M2 and DOE's self-evaluation tool. UK operators under NIS use the CAF. Manufacturers and buyers of integration services use 62443, because contracts can name a part, an SL-T and an ML. A small water utility starts with the CPGs. Large operators often report through C2M2 or the CAF and engineer to 62443.
The ten capability domains
Levels 2 and 4 sit between the descriptions shown; the roadmap below lists what moves a site up.
| Domain | Level 1 Ad hoc | Level 3 Defined | Level 5 Optimised |
|---|---|---|---|
| Governance and ownership | IT and engineering each assume the other owns OT risk | Named OT security leader and site owners; engineering signs off changes | OT risk reported to the board by consequence; cyber PHA drives investment |
| Asset inventory | Site spreadsheets, years out of date | Passive inventory with firmware, protocols, owner, criticality and device accounts | Continuously reconciled with monitoring and change records; device provenance known |
| Architecture and segmentation | Flat networks, dual-homed hosts, direct IT to OT paths | Zones and conduits documented; Level 3.5 DMZ terminates IT to OT sessions; SIS in its own zone | SL-T met per zone or gaps formally accepted; unidirectional gateways where justified |
| Remote and third-party access | Always-on vendor tools and shared VPN accounts | One DMZ broker: named accounts, MFA, approval windows, recording | Just-in-time access tied to work orders, with automatic expiry |
| OT identity and accounts | Default passwords, shared HMI and engineering logins, OT domain trusting IT | Defaults changed at commissioning; separate OT domain; service accounts owned | Individual authentication for critical operator actions; service credentials vaulted and rotated where vendors allow |
| Vulnerability and patch management | Patches applied when a vendor engineer visits | Advisories triaged against inventory; patches aligned to outages; compensating controls documented | Exposure-based prioritisation with tracked time to mitigate |
| Monitoring and detection | No OT visibility; firewall logs unread | Passive protocol-aware monitoring at key conduits; OT playbooks in the SOC | Detections tuned to ATT&CK for ICS; OT threat hunting |
| Configuration and logic integrity | No known-good copy of PLC logic or HMI images | Offline backups of logic, firmware and HMI images; changes matched to tickets | Running logic compared automatically with approved baselines |
| Incident response and recovery | IT plan only; nobody knows who can order a shutdown | OT incident plan; authority for manual operation and isolation defined; exercised with operators | Timed drills; each site can run isolated from IT for a defined period |
| Supply chain and workforce | Contracts silent on security; no OT training | 62443-2-4 terms in service contracts; role-based OT training | 4-1 and 4-2 evidence required at procurement; suppliers in exercises |
The domains cover the C2M2 domain set (ASSET, ARCHITECTURE, PROGRAM, RESPONSE, ACCESS, RISK, SITUATION, THIRD-PARTIES, THREAT, WORKFORCE) and the joint government Principles of operational technology cyber security (2024), which give two tests worth applying: "a more critical environment should never be administered from a less critical environment" and "Critical OT systems should not be reliant on IT systems to operate."
Where identity fits
Identity decides who crosses a conduit. MITRE ATT&CK for ICS (v20) records the patterns: T1694.001 Default Credentials, with procedure examples including the Unitronics Defacement Campaign (C0031) and the 2026 U.S. Water Utilities Attacks (C0066); T0859 Valid Accounts, used in the 2015 Ukraine electric power attack over VPN and by Triton's operators through RDP jump boxes; T0822 External Remote Services; and T0883 Internet Accessible Device.
- Level 2 to 3: change default passwords, broker vendor access through one DMZ path and disable accounts when contracts end; CISA lists both among five primary OT mitigations.
- Level 3 to 4: give every historian, OPC, SCADA and backup service account an owner, remove interactive logon and separate operator, engineer and administrator roles.
- Level 4 to 5: just-in-time engineering access, vaulted device credentials and certificate lifecycle management for OPC UA machine identities.
The Colonial Pipeline ransomware attack began with one unused VPN account. See the OT and ICS Identity and Access Guide, the Remote Access Identity Guide and the Service Account Security Guide. Bulk electric system entities should map this domain to CIP-005 and CIP-007; see the NERC CIP Guide.
Scoring method and evidence
- Score per site: list each site's zones, from the DMZ down to safety systems, and score every domain per site before rolling up.
- Apply a cumulative rule: as C2M2 puts it, "To earn a MIL in a given domain, an organization must perform all practices in that level and in the preceding level."
- Require evidence: a policy alone scores Level 2 at most.
- Set a target profile: C2M2 notes that "Establishing a target MIL for each domain is an effective strategy for using the model." Aim for Level 4 in remote access and segmentation at high-consequence sites, Level 3 elsewhere.
- Report the weakest link: a site's level is its lowest score among the domains a likely attack path depends on, usually remote access, identity, segmentation and recovery.
Assess with operations and engineering, and never actively scan Level 1 and 2 devices for evidence. CISA's Cyber Security Evaluation Tool (CSET) desktop tool gives a repeatable baseline. For inventory method, see the OT Asset Visibility Guide.
Self-assessment questions
- Exposure: when did you last confirm that no PLC, HMI or RTU at any site is internet-reachable, and how?
- Inventory: could you list within a day every controller running a firmware version named in a new ICS advisory, with zone and owner?
- Segmentation: does any path from corporate IT to Level 2 bypass the DMZ, including dual-homed hosts and historian links?
- Remote access: how many ways can a vendor connect, and is every session tied to a named person, MFA, an approval and a recording?
- Accounts: how many default, shared or ownerless accounts remain in OT zones, including service accounts?
- Integrity and response: when did you last restore a controller from offline backup, and who can order manual operation at 3am?
Moving up a level
Size changes the route, not the target. A small utility reaches Level 3 through the CPGs, often with an integrator held to written terms. A large operator needs a reference zone model, an SL-T library per asset type, central OT monitoring and 62443-2-4 terms in every service contract. See the Top 10 OT Security Risks for where to look first.
From Ad hoc to Developing
- Name an OT security owner and a contact at each site, with operations as co-owner.
- Remove internet exposure (CPG 2.X Limit OT Connections to Public Internet) and change default passwords (CPG 2.A) on every controller and HMI.
- Back up controller logic, firmware and HMI configurations offline.
From Developing to Defined
- Build a passive inventory from SPAN ports or taps (CPG 1.A Asset Inventory); use vendor-approved active queries only in maintenance windows.
- Document zones and conduits and build the Level 3.5 DMZ. Run new conduit rules log-only through a full production cycle, enforce one zone at a time in a planned outage with an engineer on site, and keep the previous rule set ready to restore. See the Network Segmentation Guide.
- Consolidate remote access onto one broker with phishing-resistant MFA (CPG 2.H), approval and recording; pilot with one site and one vendor before closing old paths. See the Third-Party Access Guide.
- Write and exercise an OT incident plan with authority for manual operation and isolation. See the OT Incident Response Guide.
- Start OT security training for engineers and operators (CPG 2.J).
From Defined to Managed
- Run a 62443-3-2 risk assessment for the highest-consequence area and set SL-T per zone and conduit.
- Send OT detections to the SOC, alerting on program downloads, mode changes, firmware sessions (T1693 Modify Firmware) and unexpected writes (T1692.001 Command Message). See the OT Security Platform Buyer's Guide.
- Review conduit rules, OT accounts and vendor access quarterly with named approvers.
- Time recovery drills: restore a controller and an HMI and run a unit manually; CISA's primary mitigations call manual operation capability "vital" and say fail-safe and backup arrangements "should all be routinely tested".
From Managed to Optimised
- Apply consequence-based engineering so safety in the worst scenarios does not depend on a network control.
- Compare running logic and firmware with approved baselines automatically.
- Require 4-2 capability and 4-1 processes at every refresh, and bring suppliers into exercises.
Framework mapping
NHI Mgmt Group's own mapping for orientation, not an official crosswalk.
| Domain | C2M2 | CISA CPG | IEC 62443 | NIST CSF 2.0 | NCSC CAF |
|---|---|---|---|---|---|
| Governance and ownership | PROGRAM, RISK | 1.C | 2-1 | GV.RR | A1, A2 |
| Asset inventory | ASSET | 1.A | SR 7.8 | ID.AM | A3 |
| Architecture and segmentation | ARCHITECTURE | 2.F, 2.X | 3-2, FR5 | PR.IR | B4, B5 |
| Remote and third-party access | ACCESS, THIRD-PARTIES | 2.H | SR 1.13, 2-4 | PR.AA | B2, A4 |
| OT identity and accounts | ACCESS | 2.A, 2.H | FR1, FR2 | PR.AA | B2 |
| Vulnerability and patch | THREAT | 1.E | 2-3 | ID.RA, PR.PS | B4 |
| Monitoring and detection | SITUATION | 2.T | FR6 | DE.CM | C1, C2 |
| Configuration and logic integrity | ASSET | 2.R | FR3, SR 7.3 | PR.PS | B4 |
| Incident response and recovery | RESPONSE | 2.S | FR7, SR 7.4 | RS.MA, RC.RP | D1, D2 |
| Supply chain and workforce | THIRD-PARTIES, WORKFORCE | 2.J | 2-4, 4-1, 4-2 | GV.SC, PR.AT | A4, B6 |
NIST SP 800-82 Rev. 3 provides an OT overlay for SP 800-53 Rev. 5; a Rev. 4 draft is open for comment until 30 November 2026.
Metrics that show maturity
- Exposure: internet-reachable OT devices and direct IT to OT flows (target: zero).
- Inventory coverage: percentage of OT assets with firmware, zone, owner and criticality recorded.
- Brokered access: percentage of remote sessions with a named account, MFA and recording.
- Credential hygiene: default, shared or ownerless accounts remaining in OT zones.
- Change integrity: percentage of logic and firmware changes matched to an approved ticket.
- Recovery readiness: exercised time to restore a critical controller, and hours each site can run isolated from IT.
Common failure patterns
- Averaging across sites: a group Level 3 that conceals a site with exposed PLCs and default passwords, the gap behind the Unitronics campaign and the 2026 water utility attacks.
- Confusing a certificate with maturity: an SL 2 capable controller deployed with defaults, or a supplier's ML claim accepted without asking which requirements it covers.
- Scoring policy, not practice: a remote access standard exists while engineers keep a separate vendor tool for emergencies.
- Untested IT dependence: OT segmented on paper but reliant on IT authentication, backups or business systems. Colonial Pipeline halted its pipeline as a precaution after ransomware reached only its IT systems.
Practitioner checklist
- Score all ten domains per site with evidence, jointly with operations.
- Pick one system of record (C2M2, CAF, 62443 or CPGs) and map this model to it.
- Target Level 3 in 12 months, with Level 4 for remote access and segmentation at high-consequence sites.
- Confirm monthly that no OT device is internet-reachable and no default password remains.
- Route all vendor access through one broker and give every OT service account an owner.
- Restore a controller from offline backup and drill manual operation at least yearly.
- Baseline the six metrics, report quarterly and reassess annually.
Standards and references
- US Department of Energy: Cybersecurity Capability Maturity Model (C2M2)
- IEC: IEC 62443-2-1:2024 Security program requirements for IACS asset owners
- IEC: IEC 62443-2-4:2023 Security program requirements for IACS service providers
- ISA Global Cybersecurity Alliance: Quick Start Guide, An Overview of ISA/IEC 62443 Standards
- NIST: SP 800-82 Rev. 3, Guide to Operational Technology (OT) Security
- CISA: Cross-Sector Cybersecurity Performance Goals
- NCSC: Cyber Assessment Framework
- CISA: Primary Mitigations to Reduce Cyber Threats to Operational Technology
Related NHI Mgmt Group resources: OT Security Guide · IEC 62443 Guide · OT and ICS Identity and Access Guide · OT Asset Visibility Guide · Incident Response Maturity Model