Small and rural water systems are the population attackers have actually reached, and most of the fixes that would have stopped them cost little more than an afternoon of an operator's time. This checklist sets out ten actions that a small drinking water or wastewater system can take without an in-house IT team, drawn from joint CISA, EPA and FBI guidance and from EPA inspection findings.

It is written for operators, superintendents, town and district managers, board members, and the contractors and integrators who support small utilities. It is deliberately short and practical. For the full sector picture, including chemical dosing safeguards and US regulatory detail, see the Water and Wastewater Cybersecurity Guide and the EPA Water Sector Cybersecurity Requirements Guide.

Key takeaways

  • Attacks on small water systems have mostly used simple weaknesses: devices reachable from the internet, default or missing passwords, shared logins and former staff who still have access.
  • EPA states that over 70% of systems it inspected since September 2023 violate basic Safe Drinking Water Act section 1433 requirements, and lists default passwords, single shared logins and former employee access among common findings.
  • CISA, EPA and FBI publish eight top cyber actions for water systems. This checklist covers all eight and adds two that small systems most often miss: controlling contractor remote access and knowing how to run the plant by hand.
  • Free help exists. EPA runs a technical assistance programme for the water sector, and CISA offers free cyber hygiene vulnerability scanning.
  • Write down who does each action, even if that person is a contractor. A checklist with no owner is not done.

Why small systems are targeted

Small utilities often run programmable logic controllers (PLCs) and human-machine interfaces (HMIs) installed by an integrator years ago, sometimes with a remote connection so the integrator or operator can check the plant from home. Few have dedicated IT or security staff. That combination makes them easy to find and easy to get into.

The joint advisory AA23-335A describes how actors linked to Iran's Islamic Revolutionary Guard Corps, using the CyberAv3ngers persona, targeted Unitronics Vision series PLCs and HMIs. According to the advisory, the affected devices had the default password or no password, and between November 2023 and January 2024 the actors compromised at least 75 devices, including at least 34 in the US water and wastewater sector. Reported actions included erasing ladder logic, renaming devices and displaying a defacement message on HMI screens. Hardening steps for those devices are in the Unitronics Vision and UniStream PLC Hardening Guide.

In September 2024, the City of Arkansas City, Kansas, reported a cyber security issue at its water treatment facility. In the city's press release, as published by WaterWorld, the city manager stated that the facility switched to manual operations while the situation was resolved and that the water supply remained safe with no disruption to service. The ability to run by hand is what kept service going, which is why it appears in this checklist.

EPA's enforcement alert on drinking water cyber security, issued in May 2024, adds the inspection view: common problems include failure to change default passwords, a single login for all staff, failure to remove former employees' access, and risk and resilience assessments or emergency response plans that leave out cyber resilience.

The ten actions

Actions 1 to 8 follow the order of the joint CISA, EPA and FBI fact sheet Top Cyber Actions for Securing Water Systems. Actions 9 and 10 are NHI Mgmt Group additions for small systems. The "how to do it" detail under each action is practical guidance, not text from the fact sheet.

1. Reduce exposure to the public-facing internet

No PLC, HMI or SCADA screen should be reachable directly from the internet.

  • Ask your integrator or internet provider for a list of every device with a public address or port forwarding rule at the plant, lift stations and tanks.
  • Remove port forwarding to control devices. If remote access is needed, use a VPN or remote access gateway with multi-factor authentication (see action 9).
  • Ask CISA for free cyber hygiene scanning, which reports what it can see of your systems from the internet.
  • Check again after any contractor visit or equipment change.

2. Conduct regular cybersecurity assessments

  • Use a free assessment from EPA or CISA rather than starting from scratch.
  • Do it once a year and after any significant change, such as a new SCADA system or new remote connection.
  • Keep the result with your risk and resilience assessment and emergency response plan, since EPA has found many of those leave out cyber resilience.

3. Change default passwords immediately

This is the single most important action for small systems. AA23-335A describes devices compromised because they still had the default password or none.

  • Change the password on every PLC, HMI, router, firewall, modem and remote access tool.
  • Use long, unique passwords and keep them in a password manager or sealed record that more than one trusted person can reach.
  • Ask your integrator to confirm in writing that no device still uses a factory password.
  • For background on this control, see D3-CDP Change Default Password.

4. Conduct an inventory of OT and IT assets

  • List every PLC, HMI, SCADA computer, router, modem, cellular gateway and laptop used for operations.
  • For each, record location, make and model, firmware or software version, who supports it and how it connects.
  • A spreadsheet is enough. Update it whenever equipment is added or replaced.

5. Develop and exercise incident response and recovery plans

  • Write a one-page plan: who to call, how to isolate the network, how to switch to manual control, and how to tell customers and regulators.
  • Include phone numbers for your integrator, internet provider, state primacy agency, EPA, CISA and local FBI field office.
  • Run a short tabletop exercise once a year with operators and managers. The OT Incident Response Plan Template gives a fuller structure.

6. Back up OT and IT systems

  • Back up PLC logic, HMI projects, SCADA configuration and setpoints, as well as office systems such as billing.
  • Keep at least one copy offline, for example on removable media stored securely, so ransomware cannot reach it.
  • Test a restore at least once a year. AA23-335A also recommends creating and testing backups of PLC logic and configuration. The Backup and Recovery Testing Checklist helps structure the test.

7. Reduce exposure to vulnerabilities

  • Ask your integrator to check firmware and software versions against vendor updates at least twice a year.
  • Prioritise devices that face the internet or support remote access.
  • Replace equipment that no longer receives updates when budgets allow, and list it as a risk until then. The OT Patch Management Guide covers safe update practice.

8. Conduct cybersecurity awareness training

  • Train every operator and office staff member at least once a year on phishing, password handling and reporting anything unusual on the HMI.
  • Include board members and managers who approve remote access or contracts.

9. Control contractor and remote access

Many small systems rely on an integrator who connects remotely. That connection is often the easiest way in.

  • Use one controlled remote access method, protected by multi-factor authentication. AA23-335A recommends multi-factor authentication for OT network access and routing remote access through a VPN, gateway or proxy.
  • Give each person their own account. EPA lists single shared logins as a common inspection finding.
  • Remove access the day an employee or contractor leaves. EPA lists failure to curtail former employees' access as a common finding.
  • Turn remote access off when not in use, or require the utility to approve each session. The OT Remote Access Guide covers options in more depth.

10. Be able to run the plant by hand

  • Write down manual operating procedures for each critical process: pumping, chemical feed, filtration and disinfection.
  • Practise them at least once a year, including on a night or weekend shift.
  • Make sure operators know how to spot signs of tampering on the HMI, such as changed setpoints, renamed devices or unfamiliar messages, and to switch to manual and call for help if they see them.
  • Arkansas City's switch to manual operations is the example to aim for: service continued while the incident was handled.

Using the checklist without IT staff

Most small utilities will rely on a mix of operators, a contractor and free public services. A practical approach:

  • Name an owner for each action. The owner can be a contractor, but someone at the utility must check it is done.
  • Put security in the integrator contract. Ask for written confirmation of default password changes, a current asset list, backups of logic and configuration, and notice before any new remote connection.
  • Use free help first. EPA's enforcement alert points utilities to the EPA Cybersecurity Technical Assistance Program for the water sector, and to CISA cyber hygiene services, requested by emailing [email protected] with the subject line "Requesting Cyber Hygiene Services".
  • Contact your regional CISA cyber security advisor. The CISA fact sheet tells water systems needing help to contact EPA or their regional CISA cyber security advisor.
  • Report to the board. Give the board or council a one-page status against the ten actions twice a year.

Regulatory context for US community water systems

EPA's enforcement alert states that community water systems serving more than 3,300 people must carry out risk and resilience assessments and emergency response plans under Safe Drinking Water Act section 1433, certify completion to EPA, and review them every five years. EPA also states it has taken more than 100 enforcement actions for section 1433 violations since 2020. Smaller systems below that threshold are not covered by those requirements but face the same threats, so the ten actions apply regardless of size. This is general information, not legal advice; for the full picture see the EPA Water Sector Cybersecurity Requirements Guide.

A simple status table

Copy this table into a spreadsheet and fill in an owner, status and date for each row.

ActionOwnerEvidence of doneReview
1. No control devices on the internetOperator and integratorClean CISA scan reportEvery 6 months
2. Annual assessmentManagerAssessment report filed with risk assessmentAnnually
3. Default passwords changedIntegratorSigned confirmation per deviceAfter every change
4. Asset inventoryOperatorDated spreadsheetEvery 6 months
5. Incident plan exercisedManagerExercise notesAnnually
6. Backups testedIntegratorRestore test recordAnnually
7. Updates reviewedIntegratorVersion check recordEvery 6 months
8. Training completedManagerAttendance listAnnually
9. Remote access controlledManager and integratorAccount list with multi-factor authentication confirmedQuarterly
10. Manual operations practisedLead operatorDrill recordAnnually

Framework mapping

ActionReference
Remove internet exposureMITRE ATT&CK for ICS T0883 Internet Accessible Device
Change default passwords, individual accountsATT&CK for ICS T0859 Valid Accounts; mitigation M1027 Password Policies
Control remote access with multi-factor authenticationATT&CK for ICS T0886 Remote Services; mitigation M1032 Multi-factor Authentication
Asset inventoryNIST CSF 2.0 ID.AM-01
BackupsNIST CSF 2.0 PR.DS-11; mitigation M1053 Data Backup
Incident and recovery plansNIST CSF 2.0 ID.IM-04 and RC.RP-01
TrainingNIST CSF 2.0 PR.AT-01
Manual operations against tamperingATT&CK for ICS T0831 Manipulation of Control

Signs that something is wrong

Small systems rarely have security monitoring, so operators are the detection system. AA23-335A describes actors renaming devices, erasing logic and leaving messages on HMI screens. Train operators to treat these as possible cyber incidents, not equipment faults:

  • Unfamiliar messages, logos or text on an HMI screen.
  • Devices with new names, or setpoints and alarm limits that nobody on shift changed.
  • A PLC that will not accept a program upload or download, or has lost its logic.
  • Remote access sessions at times when no contractor was booked.
  • Passwords that suddenly stop working for several staff at once.

If any of these appear, switch the affected process to manual control, disconnect remote access, keep the equipment powered for investigation where safe to do so, and follow your incident plan. The OT Incident Response Guide describes the wider response steps.

Common failure patterns

  • An HMI or PLC left on a public address so the integrator can check it remotely.
  • Factory passwords still in place because "nobody knows what it is set to".
  • One shared login used by every operator and the contractor.
  • Former operators and contractors who can still connect months after leaving.
  • No offline copy of PLC logic, so a wiped controller has to be reprogrammed from scratch.
  • Manual procedures that exist only in a senior operator's head.
  • An emergency response plan that does not mention cyber incidents at all.
  • Assuming the utility is too small to be a target.

Practitioner checklist

  • Confirm no PLC, HMI or SCADA computer is reachable from the internet, and request a CISA cyber hygiene scan.
  • Change every default password and get written confirmation from your integrator.
  • Give every operator and contractor their own account and remove leavers the same day.
  • Put all remote access behind one VPN or gateway with multi-factor authentication.
  • Keep a dated inventory of all control and network equipment.
  • Back up PLC logic and HMI projects offline and test a restore each year.
  • Write and exercise a one-page cyber incident plan with phone numbers.
  • Practise running each critical process by hand at least once a year.
  • Train staff and board members annually.
  • Ask EPA for free technical assistance and report status to the board twice a year.

Standards and references

Related NHI Mgmt Group resources: Water and Wastewater Cybersecurity Guide · EPA Water Sector Cybersecurity Requirements Guide · OT Remote Access Guide · OT Ransomware Response Playbook

PDF for subscribers

Take this guide with you

Every section, table and checklist in one PDF, with links to the sources and related guides. Subscribe to our weekly NHI & AI Identity Journal and we’ll email you a download link.

Free weekly newsletter

Subscribe to the NHI & AI Identity Journal

The latest on NHI and Agentic AI security – articles, research, breaches, news and events every week.

Bonus 33% off our NHI Course when you subscribe.

PDF Downloads for Newsletter Subscribers

Get the guide

Enter your details and we’ll email you a download link.

The full guide is free to read online. The PDF is a thank you for subscribing.

Fill in all fields marked * and tick both boxes to continue.