Unitronics Vision and UniStream controllers are safe to run on a water, food or energy site only when the default password is gone, the controller is off the public internet, the firmware and engineering software are current and someone is watching for logic changes. This guide turns the joint CISA advisory on the CyberAv3ngers campaign and Unitronics' own cyber protection pages into a hardening baseline that an OT engineer, integrator or security team can apply controller by controller. It covers defensive steps only: credentials, exposure, firmware, remote access, backups and detection.
The campaign that made these controllers famous was not technically sophisticated. According to CISA advisory AA23-335A, IRGC-affiliated actors reached internet-exposed Vision Series PLCs and HMIs that still had a default password or no password at all, and communicated with them over the default TCP port 20256. The fixes are therefore mostly configuration and network hygiene, which is good news: nearly every step here can be done without new products.
This is an independent guide from NHI Mgmt Group, based on Unitronics' public documentation as of November 2026. It is not sponsored or reviewed by Unitronics. Product features change, so confirm settings against Unitronics' current documentation.
Key takeaways
- The CyberAv3ngers intrusions relied on internet exposure plus default or missing passwords. CISA reports at least 75 compromised Unitronics devices in the United States, including at least 34 in the water and wastewater sector.
- CVE-2023-6448 (insecure default, CVSS 9.8) affects VisiLogic before 9.9.00 and Vision OS before 12.38. Upgrade VisiLogic to 9.9.00 or later and move every Vision controller to the newest firmware for its model.
- Set every password layer on Vision projects, not just one: TCP/IP (PCOM socket), upload project, INFO mode and SD card passwords, as the CISA advisory lists.
- For UniStream, change the default PLC passwords, set an access password for UniLogic connections, protect VNC, require FTP authentication and assign users to HMI and web server screens. Unitronics recommends controllers and tools at version 1.35.227 and above.
- No PLC should be reachable from the internet. Remove port forwarding, put the controller behind a firewall and make remote access go through a VPN or gateway with multifactor authentication.
- Treat the engineering workstation and the controller password as non-human credentials: inventory them, store them in a vault, rotate them when people leave and log who uses them.
- Keep tested offline backups of ladder logic and configuration. In the campaign, actors replaced logic and deliberately left victims unable to retrieve it.
What happened in the CyberAv3ngers campaign
CISA, the FBI, NSA, EPA and partners first published AA23-335A on 1 December 2023, updated it on 14 December 2023 with CVE and patch details and updated it again on 18 December 2024. The advisory describes IRGC-affiliated actors, publicly known as CyberAv3ngers, accessing multiple United States water and wastewater facilities from 22 November 2023 that used Unitronics Vision Series PLCs with built-in HMIs. The activity continued in waves into January 2024 and also touched energy, food and beverage manufacturing, transportation and healthcare. The December 2024 update notes that older Unitronics models and rebranded Vision devices were also compromised.
The impact described is the reason this matters to defenders. On affected devices the actors replaced the original ladder logic with logic that had no inputs or outputs, renamed devices, changed the communication port from 20256 to 20257, disabled upload and download, set upload password protection and displayed a defacement screen on the HMI with the message "You have been hacked, down with Israel." Operators lost visibility of normal readings and, in some cases, the ability to connect their own engineering software. CISA warns that deeper access could allow more serious cyber physical effects.
The CISA advisory maps the activity to MITRE ATT&CK Enterprise techniques including brute force, default accounts (T1078.001) and internal defacement (T1491.001). In ATT&CK for ICS terms, the same pattern lines up with Internet Accessible Device (T0883), Valid Accounts (T0859) and Program Download (T0843). For the actor itself, see the CyberAv3ngers Threat Actor Profile Guide; this page stays on the controller.
Know what you have: Vision, Samba and UniStream
Hardening starts with an accurate list. Many sites bought these controllers through an integrator or as part of a skid from an equipment supplier, and some carry another brand's label. Build a register that answers, for each controller:
- Family and model (Vision, Samba or UniStream), firmware or OS version and the version of VisiLogic or UniLogic used to program it.
- Network path: which interface is connected, which IP address, whether a cellular modem or router sits in front of it, and whether any port forwarding or NAT rule points at it.
- Who can program it: in-house engineers, the integrator, the equipment supplier, and from which workstations.
- Where the current project file and the last known good backup are stored.
- Which passwords are set, who knows them and where they are recorded.
The CISA advisory asks owners to keep asset management processes running and to inventory internet-accessible devices periodically. A simple, reliable way to do the second part is an external exposure check of your own address ranges by your security team or service provider, plus a review of every cellular router and remote access box on site. The OT Asset Visibility Guide covers passive discovery if you need a wider picture.
Remove internet exposure first
If a controller is reachable from the public internet, fix that before anything else. CISA's immediate steps are to disconnect PLCs from the public internet or, where remote programming is unavoidable, disable it or protect it with a strong password, and to place devices behind a firewall that can detect brute force attempts. Unitronics' own guidance for both Vision and UniStream says the same in plainer terms: ensure all equipment is behind a firewall and verify that no port forwarding settings expose automation equipment directly to the public network.
Practical steps:
- Check every router, firewall and cellular modem in front of a Unitronics controller for port forwarding, DMZ host or "virtual server" rules. Remove any that point at a PLC or HMI.
- Block inbound traffic to TCP 20256 (the default PCOM port) and any custom PCOM port at the perimeter. CISA notes that actors actively targeted TCP 20256.
- Design the controller as a client. Unitronics recommends reducing sockets in server mode, configuring unused sockets as client, and making sure that where the controller must reach internet resources it initiates the connection.
- Block unnecessary ports at both external and internal firewalls, and block unused high ephemeral ports, as CISA recommends.
- Repeat the external exposure check after the change and on a schedule, because integrators and suppliers sometimes reopen access for support.
Credentials and password layers
CVE-2023-6448 is classified by CISA as CWE-1188, initialisation of a resource with an insecure default. The CISA ICS advisory tells users who cannot update to change all default passwords and confirm that the default password 1111 is not in use. Treat that check as mandatory even after upgrading.
Vision and Samba
The AA23-335A immediate steps ask owners to apply security elements to project files, including:
- TCP/IP password on PCOM-enabled sockets, so network clients must authenticate before talking to the controller.
- Upload project file password, so the logic cannot be pulled off the controller by anyone with network access.
- INFO mode password, protecting the controller's on-device information and settings mode.
- SD card password, protecting data and project content written to removable storage.
Unitronics' Vision and Samba page describes tiered PCOM access levels: blocked, operator (view and update data) and technician (troubleshooting, settings changes and version updates). It recommends keeping access blocked until there is a need for viewing only. The CISA ICS advisory also points to restricting remote PCOM operations using SDW10 roles, and Unitronics documents SB 314 and SDW 10 for configuring multifactor authentication on Vision and Samba devices. Follow the VisiLogic help for the exact steps for your model.
If the controller acts as a Modbus slave, Unitronics recommends limiting the address space available to a Modbus master by enabling SB 305 and setting SI 165 to SI 168. That reduces what a rogue master can read or write even if it reaches the network.
UniStream
Unitronics' UniStream page lists these controls:
- Change the PLC default passwords and store them according to accepted practice.
- Set a new access password, which prevents a casual user from connecting to the controller through UniLogic.
- Set users and permissions for HMI screens through User Access Control, and for web server screens.
- Set UniApps permissions through Password Management.
- Set VNC passwords through VNC Server Management.
- Set authentication for the FTP server, which Unitronics describes as mandatory.
Treat controller passwords as machine credentials
A PLC password is a shared secret used by software, engineering workstations and often by an integrator's laptop. That makes it a non-human credential in practice. Store each controller's passwords in a vault or a controlled register rather than in the project file notes or on a label on the panel, give each site or controller its own values instead of one password across the estate, and rotate them when an engineer or integrator leaves. CISA also recommends centralised authentication for controller accounts where it is available and disabling unused authentication methods and default keys. The OT and ICS Identity and Access Guide covers how to run that process across vendors.
Firmware and engineering software
The CISA ICS advisory for CVE-2023-6448 lists VisiLogic versions before 9.9.00 and Vision OS versions before 12.38 as affected, and states that Unitronics patched the issue in VisiLogic 9.9.00. AA23-335A asks owners to upgrade engineering workstations to VisiLogic 9.9.00 and to upgrade every Vision PLC and HMI to the newest firmware for its model, setting a strong password as part of the process. Unitronics' Vision page notes that VisiLogic 9.9.00 includes built-in security enhancements. For UniStream, Unitronics recommends updating controllers and development tools to version 1.35.227 and above, and reviewing release notes for security information.
Plan updates as you would any OT change:
- Back up the running logic and configuration first (see the backup section below).
- Read the release notes for the target version and confirm compatibility with any HMI projects, communication drivers and connected devices.
- Update the engineering workstation software, then the controller, during a planned window with operations aware.
- Set or reset passwords during the update rather than leaving it for later.
- Record the new version in the asset register and subscribe to Unitronics' security advisories so the next update is not missed.
The CISA ICS advisory also asks owners to confirm that third-party vendors apply these countermeasures. If a supplier maintains your controllers, ask them in writing which versions they are running and when they last changed the passwords. The ICS Advisory Triage and OT Vulnerability Management Guide explains how to prioritise advisories like this one across a mixed estate.
Safe remote access
Most small water utilities and plants exposed these controllers because someone needed remote access. The answer is to change how remote access works, not to remove it. CISA recommends multifactor authentication for all remote access to the OT network and, where remote access is needed, a VPN, gateway or proxy that supports MFA. The CISA ICS advisory adds that a VPN is only as secure as the devices connected to it, so keep the VPN and the connecting laptops patched.
Unitronics' own pages describe two vendor routes: its UCR industrial routers, which include firewall and VPN functions, and UniCloud, which allows connection without a fixed or public IP address and restricts access by permission level while tracking connections. Unitronics' general cybersecurity page also recommends VPN with two-factor authentication for remote access and says remote management should not be enabled on network equipment itself.
Whatever route you choose, apply the same rules:
- Named accounts for each engineer and each supplier, with MFA, instead of a shared login.
- Access that is switched on for a maintenance window and switched off afterwards where possible.
- A host-based allowlist on or in front of the controller, so it accepts connections only from known engineering workstations, as CISA recommends.
- Session records kept long enough to investigate a logic change weeks later.
The OT Remote Access Guide goes deeper into architecture choices.
Change defaults: port, device name and mode control
CISA's immediate steps include changing the default port and the default device name. Neither is a strong control on its own, and a determined actor can scan for other ports, but moving off TCP 20256 removes the device from the cheapest automated scans and a non-default name is needed for remote connections. Record the new values in the asset register so your own engineers are not locked out.
CISA also recommends limiting operating mode changes to authenticated users with role-based controls, considering physical keys where the hardware supports them, and authenticating all access to field controllers before allowing changes to state, logic or programs. On Vision and Samba, the PCOM access levels and SDW10 roles are the relevant settings; on UniStream, use the access password and User Access Control.
Backups and recovery readiness
The campaign showed why backups matter for PLCs specifically. CISA reports that the actors did not burn the replacement ladder logic to the device, which prevented victims from retrieving it, and that they changed settings so engineering workstations could no longer communicate. A site with a current, tested backup and a known reset process recovers in hours; a site without one may need the integrator to rebuild the project.
- Create and test backups of PLC logic and configuration, as both CISA advisories recommend, and keep at least one copy offline.
- Learn and document the factory reset and redeployment process for each model before you need it.
- Keep cold standby or replacement hardware for critical controllers, as AA23-335A recommends.
- Compare the running logic with the stored backup after any remote session or supplier visit.
The OT Backup, Recovery and Golden Image Guide covers retention and testing in more detail.
Logging and detection
Small controllers produce limited logs, so detection mostly happens on the network and in the tools around the PLC. AA23-335A recommends that defenders:
- Monitor network traffic for unusual logins, unexpected protocols, mode-changing or program-modifying functions and protocols on mismatched ports.
- Monitor for standard protocols on non-standard ports.
- Deploy intrusion detection and prevention systems on OT networks.
- Apply rules that block repeated login attempts and use watchdog timers to detect unresponsive systems.
- Monitor asset management systems for configuration changes.
Turn those into concrete signals for a Unitronics estate. These are illustrative detections to adapt to your own tooling:
| Signal | Where to see it | Why it matters |
|---|---|---|
| Any inbound connection to TCP 20256 or your custom PCOM port from outside the OT network | Perimeter firewall logs, cellular router logs | The campaign used this port; legitimate access should come through the VPN or gateway. |
| PCOM traffic from a host not on the engineering workstation allowlist | OT network monitoring, internal firewall | Unexpected clients are the first sign of misuse or an unmanaged laptop. |
| Program download or upload outside a change window | OT monitoring that decodes the protocol, remote access session records | Logic replacement was the main impact in the campaign. |
| Device name or port change on a controller | Configuration comparison against the asset register | Actors renamed devices and moved the port to 20257. |
| Repeated failed authentication on a VPN, gateway or UniCloud account | Remote access platform logs | Brute force against remote access precedes access to the PLC. |
| HMI screen showing unexpected content or the controller stops responding | Operator reports, watchdog timers, SCADA polling alarms | Defacement and loss of view were visible symptoms. |
Make sure operators know that an unexpected HMI screen is a security event and who to call. CISA asks United States organisations to report incidents to its 24/7 operations centre or the local FBI field office.
Common failure patterns
- A cellular router nobody owns. The integrator installed a modem with port forwarding for support, and it is not on any IT or OT asset list.
- Only one password layer set. A TCP/IP password is configured, but upload, INFO mode and SD card passwords are still empty.
- Updated software, old controllers. VisiLogic was upgraded on one laptop, but controllers in the field still run old firmware.
- One password for the whole estate. Every controller shares the same password, and it is known to former staff and several suppliers.
- Backups that are never tested. The project file on the engineering laptop is older than the running logic, or nobody knows the reset procedure.
- Remote access left on. A VPN or cloud connection set up for a one-off fix stays permanently enabled without MFA.
- Defacement treated as a fault. Operators reboot the HMI and carry on, destroying evidence and missing that logic has changed.
Practitioner checklist
- Build a register of every Unitronics controller with model, firmware, software version, network path, owner and password status.
- Run an external exposure check and remove every port forwarding or NAT rule that reaches a PLC or HMI.
- Block TCP 20256 and any custom PCOM port at the perimeter, and allowlist engineering workstations internally.
- Confirm no controller uses the default password 1111 or has no password.
- On Vision and Samba, set TCP/IP, upload, INFO mode and SD card passwords and restrict PCOM access levels.
- On UniStream, change default passwords, set the UniLogic access password, VNC password and FTP authentication, and assign User Access Control.
- Upgrade VisiLogic to 9.9.00 or later, Vision firmware to the newest version per model and UniStream to 1.35.227 or later.
- Route all remote access through a VPN or gateway with named accounts and MFA, and switch it off when not needed.
- Change the default port and device name, and record both.
- Keep tested offline backups of logic and configuration and document the reset process.
- Alert on PCOM traffic from unknown hosts, program changes outside change windows and repeated remote access failures.
- Ask every supplier who maintains your controllers to confirm in writing that these countermeasures are applied.
Standards and references
- CISA: AA23-335A IRGC-Affiliated Cyber Actors Exploit PLCs in Multiple Sectors
- CISA: ICS advisory ICSA-23-348-15, Unitronics Vision and Samba Series (CVE-2023-6448)
- Unitronics: Cyber Protection for Vision and Samba
- Unitronics: Cyber Protection for UniStream
- Unitronics: Cybersecurity
- CISA, FBI, EPA and DOE: Primary Mitigations to Reduce Cyber Threats to Operational Technology
- NIST: SP 800-82 Rev. 3, Guide to Operational Technology (OT) Security
- MITRE ATT&CK: ICS Matrix
Related NHI Mgmt Group resources: PLC Security Guide · CyberAv3ngers Threat Actor Profile Guide · Water and Wastewater Cybersecurity Guide · Top 20 Secure PLC Coding Practices Explained for Engineers