An information risk assessment asks what happens to data; a cyber-physical risk assessment asks what happens to people, plant and the environment when a control system does the wrong thing, and using the first method on the second problem produces confident but wrong priorities. NIST SP 800-82 Rev. 3 notes that logic running in operational technology (OT) has a direct effect on the physical world, and lists risks to human health and safety, serious environmental damage and production loss among the consequences of OT incidents. This guide compares the two kinds of risk: consequence types, the shift from CIA to safety-first priorities, the assessment methods each uses (ISO/IEC 27005 and NIST SP 800-30 on one side, ISA/IEC 62443-3-2, cyber process hazard analysis and Consequence-driven Cyber-informed Engineering on the other) and the control trade-offs that follow. It is for risk managers, OT security leads, process safety engineers and CISOs who now own both estates. For the wider OT programme see the OT Security Guide.
Key takeaways
- The short answer: information risk is measured in lost confidentiality, integrity or availability of data and services; cyber-physical risk is measured in injury, environmental release, equipment damage and loss of an essential service, and is assessed with the plant's safety case, not beside it.
- Priorities invert, but not simply. NIST SP 800-82 Rev. 3 says OT security objectives typically prioritise integrity and availability, followed by confidentiality, with safety as an overarching priority. Read "AIC" as "safety first, then control of the process".
- Likelihood behaves differently. Safety studies assume random failures with known rates; an adversary is not random. UK HSE guidance (OG86) says standard hazard studies such as HAZOP generally do not consider multiple simultaneous contingencies or the capabilities of malicious actors.
- Methods exist for both and should be joined. Use the enterprise method for the IT estate, ISA/IEC 62443-3-2 for zones and conduits, cyber PHA to bring cyber into the hazard register, and CCE for the handful of events that would be catastrophic.
- Controls trade off differently. An information control that blocks or reboots can itself cause a physical hazard; in OT, prefer engineered and non-digital safeguards that work even when the network is compromised.
Two kinds of risk, defined
- Information risk: the effect of uncertainty on information assets and the services built on them. Impact is expressed as loss of confidentiality, integrity or availability, and the harm lands on the organisation (fines, fraud, outage cost) or on data subjects. NIST SP 800-30 Rev. 1, Guide for Conducting Risk Assessments, and ISO/IEC 27005 are the reference methods.
- Cyber-physical risk: the risk that a cyber event causes a control or safety system to act, or fail to act, in a way that changes the physical process. Harm lands on people on and off site, the environment, equipment and the communities that depend on the service. NIST SP 800-82 Rev. 3 says OT safety impacts are judged by the potential for injury, illness or death if the system malfunctions after a cyber incident, and that analyses should also cover environmental effects.
- Where they overlap: the same intrusion can carry both. The Colonial Pipeline ransomware attack was an IT-side intrusion, yet the company shut its pipeline down as a precaution, and fuel supply along the US eastern seaboard was disrupted for days. An information risk register that rated the billing systems "moderate" would have missed the physical consequence of losing them.
Consequence types compared
| Consequence | Information risk view | Cyber-physical risk view |
|---|---|---|
| Human safety | Rarely in scope; may appear under health data or life-safety alarms in buildings | Primary: injury, illness or fatality to workers and the public |
| Environment | Not usually rated | Releases, spills and emissions, rated by size, duration and regulator response |
| Equipment and plant | Hardware replacement cost | Physical damage with long lead times (transformers, turbines, kilns), which drives recovery time |
| Service delivery | Outage of a digital service, often hours | Loss of an essential service (power, water, fuel, medicines) affecting society, often days |
| Data | Primary: theft, exposure, corruption | Secondary, except where stolen data enables an attack (drawings, recipes, set points) or data integrity drives the process |
| Financial | Fines, fraud, response and outage cost | Lost production, product quality, contractual penalties, plus all the information-side costs |
| Legal and regulatory | Data protection and sector rules | Safety and environmental regulation (for example COMAH sites in Great Britain), plus network and information systems rules |
NIST SP 800-82 Rev. 3 gives example impact level definitions for OT that show the change in scale. For people on site it suggests that a fatality is High, a lost workday or major injury is Moderate and first aid or a recordable injury is Low; for cost, over 25% of revenue is High and over 5% is Moderate; for the environment, a regional agency citation or long-term damage over a large area is High. Calibrate these to your own sector before you use them.
From CIA to safety first
The CIA triad is a useful checklist in both worlds, but the ordering and meaning change.
| Property | What it means in an information system | What it means in a control system |
|---|---|---|
| Safety (overarching) | Not usually a security property | The process stays within safe limits and can always reach a safe state |
| Integrity | Data and records are accurate and unaltered | Commands, set points, logic and sensor values are genuine; the operator's view matches reality |
| Availability | Services are reachable within agreed hours | Control and view are continuous and deterministic; NIST notes high delay or jitter is unacceptable in OT, and a reboot may not be acceptable |
| Confidentiality | Usually the lead concern | Lower, but still matters for engineering files, credentials and process recipes that enable later attacks |
MITRE ATT&CK for ICS expresses the physical end state as Impact techniques such as T0880 Loss of Safety, T0879 Damage to Property, T0827 Loss of Control, T0831 Manipulation of Control and T0837 Loss of Protection. These are useful scenario labels for a cyber-physical register; the enterprise matrix does not have equivalents for most of them.
Assessment methods side by side
| Method | Domain | Unit of analysis | How likelihood is treated | Output |
|---|---|---|---|---|
| NIST SP 800-30 Rev. 1 | Information | Threat events against systems and organisations, across three tiers | Threat source capability, intent and targeting, plus vulnerability | Risk ratings that feed risk response decisions |
| ISO/IEC 27005 | Information | Information assets or events and their consequences | Qualitative or quantitative likelihood | Risk register supporting the ISO/IEC 27001 risk treatment plan |
| FAIR and cyber risk quantification | Mainly information | Loss scenarios | Frequency ranges from data and expert estimates | Annualised loss in money |
| ISA/IEC 62443-3-2 | Cyber-physical | The system under consideration, partitioned into zones and conduits | Initial assessment on worst-case unmitigated consequence, then detailed threat-based assessment | Target security level (SL-T) per zone and conduit, and security requirements |
| Cyber PHA (cyber HAZOP) | Cyber-physical | Process nodes and deviations from the existing hazard study | Adversary capability rather than random failure rates | Cyber scenarios in the hazard register, with safeguards and their cyber dependence |
| CCE (Idaho National Laboratory) | Cyber-physical | A small number of high-consequence events | Assumes a capable, targeted adversary will get in | Engineered mitigations that remove or bound the consequence |
ISA/IEC 62443-3-2 in one paragraph
ISA lists ANSI/ISA-62443-3-2-2020 as "Security risk assessment for system design" and describes the series as bridging process safety and cyber security. The method defines the system under consideration, runs an initial risk assessment on worst-case consequences, partitions the system into zones and conduits, compares initial risk with the asset owner's tolerable risk, carries out a detailed risk assessment where needed and records target security levels and requirements for each zone. For the step-by-step method see the IEC 62443-3-2 OT Risk Assessment Guide.
Cyber PHA and the safety case
HSE OG86 Edition 2, written for major accident hazard sites, says risk is assessed at zone level without credit for existing countermeasures, that each zone is classed by consequence (major accident, loss of essential service, or neither), and that a zone able to defeat a safety function, such as a basic process control system able to override a safety instrumented system, makes both zones critical. It also says following the guidance can meet the cyber requirement in clause 8.2.4 of BS EN 61511 for safety instrumented systems. NIST SP 800-82 Rev. 3 similarly suggests adding cyber scenarios to process hazard analysis or FMEA. See the OT Cyber Physical Risk and Safety Guide.
CCE for the events that cannot happen
Idaho National Laboratory describes CCE as starting from an organisation's most critical functions, assuming that a targeted network can and will be penetrated, and "engineering out" risk through design rather than relying only on cyber controls. INL summarises the relationship as Cyber-Informed Engineering being the what and CCE a how. See the Consequence-driven OT Risk (CCE) Guide.
Why likelihood and scoring break when copied across
- Random versus intelligent failure: safety integrity relies on probabilities of failure on demand for independent faults. An adversary can cause several "independent" failures at once, which is exactly what OG86 says traditional hazard studies do not consider.
- Credit for controls: information risk methods usually rate residual risk after controls. OG86 asks for zone risk without credit for existing countermeasures, then matches countermeasures to threat scenarios, because a control that shares a network with the thing it protects may fail with it.
- Heat-map compression: a five-by-five matrix tuned for data breaches places "fatality, rare" and "minor outage, frequent" in similar cells. Use the safety organisation's risk matrix and tolerability criteria for physical consequences.
- Money as the only unit: loss quantification is valuable for the business case, but safety and environmental consequences are governed by tolerability criteria and regulation, not by expected loss alone. See FAIR vs NIST SP 800-30 for the information side.
- Short time horizons: OT components typically last 10 to 15 years against 3 to 5 for IT, according to NIST SP 800-82 Rev. 3, so a risk accepted today may stand for a decade.
Control trade-offs
| Control | Information risk default | Cyber-physical consideration |
|---|---|---|
| Patching | Apply promptly, often automatically | NIST notes OT changes need thorough testing and incremental deployment; outages may need planning days or weeks ahead. Compensate with segmentation while waiting |
| Account lockout | Lock after failed attempts | Locking an operator out of an HMI during an upset is itself a hazard; use monitored shared consoles or physical controls instead |
| Automated blocking and isolation | Isolate the host on detection | Isolating a controller or HMI can lose view or control; pre-agree which assets may be isolated and by whom |
| Endpoint agents | Deploy everywhere | NIST notes OT devices may lack memory and compute for added security features; use allowlisting on supported hosts and passive network monitoring elsewhere |
| Encryption | Encrypt by default | Integrity and authentication of commands usually matter more than secrecy; latency and legacy protocol support must be tested |
| Safety systems | Not applicable | Keep the safety instrumented system separate from control; NIST warns that combining control and safety functions could let an attacker reach both |
| Non-digital safeguards | Not applicable | NIST lists analogue displays, manual controls and mechanical devices such as relief valves as limits on attack impact; credit them in the assessment |
For the related split between safety and control layers, see Safety Instrumented Systems vs Basic Process Control.
How to run a joined-up assessment
- Agree the consequence scale. Extend the enterprise risk matrix with the safety organisation's categories for people, environment, plant and essential service. One scale, signed off by the risk owner and the process safety lead.
- Map dependencies across the boundary. List IT systems that OT relies on to operate or to bill and dispatch (historians, scheduling, ERP, identity, remote access). Colonial Pipeline shows why these belong in the cyber-physical view.
- Run the initial assessment per zone on unmitigated consequence. Use ISA/IEC 62443-3-2 zones; rate each without credit for countermeasures, as OG86 does.
- Bring cyber scenarios into the hazard register. Hold a cyber PHA with operations, process safety and OT security on high-consequence nodes; record which safeguards depend on networked components.
- Select the few events for CCE. For events with unacceptable consequences, look for engineered mitigations (mechanical limits, hard-wired trips, physical interlocks) that hold even under compromise.
- Set target security levels and controls. Assign SL-T per zone and conduit, then select controls, testing each for safety side effects before deployment.
- Pilot, verify and record. Validate on one unit or site first, use passive monitoring before active controls, and keep a rollback for every change under management of change.
- Feed the result to both registers. Enterprise risk sees the money and service view; the safety case sees the hazard view. Review on any process change and at least annually.
When to use each approach
- Information risk methods alone: corporate IT, OT-adjacent business systems with no route to the process and no operational dependence, and data-centric risks such as theft of engineering IP.
- ISA/IEC 62443-3-2: any control system design, upgrade or new project, and when you need defensible zone requirements for suppliers. See the IEC 62443 Guide.
- Cyber PHA: process industries with an existing HAZOP and LOPA culture, and major hazard sites where the regulator expects cyber in the safety case.
- CCE: critical infrastructure and sites where a single event could be catastrophic or nationally significant; it is resource-intensive, so apply it to a short list.
- Small organisations: a manufacturer with one plant can run a one-day joint workshop using 800-82 impact levels and a zone diagram, then act on the top five scenarios. Large operators should formalise the shared consequence scale and run CCE centrally on fleet-wide events.
Worked scenario: chlorine dosing at a water works
An information risk review rates the SCADA historian as "medium": it holds no personal data and has backups. The cyber-physical review asks a different question. The historian sits in a zone with a conduit to the dosing PLC, and an engineering workstation in the same zone can change dosing set points. Unmitigated consequence: overdosing or underdosing of drinking water, which is a public health event (High). Cyber PHA shows that the high-level alarm and the dosing pump interlock both run through the same PLC, so they are not independent of a cyber compromise. The outcome is a separate zone for the dosing controller with a one-way data flow to the historian, an analyser-driven hard-wired trip on the dosing pump, authenticated engineering access through a jump host, and a manual sampling procedure as the last safeguard. The information risk rating of the historian did not change; the cyber-physical rating of the dosing function fell from High to Low.
Where identity fits
Many cyber-physical scenarios start with an identity: a vendor remote access account, a shared engineering workstation login or a service account the historian uses to pull data from controllers. Rate these accounts by the consequence of the zone they reach, not by the data they touch. See the OT and ICS Identity and Access Guide.
Detection and measurement
- Coverage of high-consequence functions: share of functions rated High for safety or environment that have a completed cyber PHA or CCE review.
- Cyber-independent safeguards: share of High scenarios with at least one safeguard that does not depend on a networked component.
- Zones with agreed SL-T: percentage of zones and conduits with a documented target security level and gap list.
- Cross-boundary dependencies registered: count of IT systems whose loss would force an operational shutdown, each with an owner and recovery plan.
- Monitoring of safety-relevant conduits: share of conduits to safety and control zones covered by passive network monitoring with alerts reviewed by operations.
- Gap closure: justified and approved gaps tracked to closure, as OG86 expects for major accident consequences.
Common failure patterns
- Rating OT assets by the data they hold: a controller with no sensitive data scores low on CIA, yet can cause a release. Rate by consequence.
- Leaving IT dependencies out of the OT view: the physical disruption at Colonial Pipeline came from a containment decision after an IT intrusion, not from attackers touching pipeline controls.
- Crediting safeguards that share the attack path: an alarm and a trip in the same programmable controller are not two independent layers against a cyber cause.
- Running the assessment without process safety: security teams alone miss hazards; safety teams alone miss adversary capability. Hold joint workshops.
- Importing IT response playbooks unchanged: automatic isolation or forced password resets during an upset can create the hazard you are trying to prevent. See the OT Incident Response Guide.
- One-off assessments: a process change, new remote access path or controller upgrade alters the risk; tie reassessment to management of change.
Framework mapping
| Framework | Reference | Relevance |
|---|---|---|
| NIST SP 800-82 Rev. 3 | Section 4 OT risk management; Table 3 impact levels | Safety, environmental and physical consequences in OT risk |
| ISA/IEC 62443 | Part 3-2 security risk assessment for system design; Part 3-3 system security requirements and security levels | Zone and conduit risk, SL-T |
| IEC 61511 (BS EN 61511) | Clause 8.2.4 security risk assessment for SIS, as referenced by HSE OG86 | Cyber risk in the safety lifecycle |
| NIST CSF 2.0 | GV.RM-01; ID.AM-05; ID.RA-04; ID.RA-05; PR.IR-03 | Risk objectives, criticality, impact, prioritisation, resilience |
| NIST SP 800-53 Rev. 5 | RA-2 Security Categorization; RA-3 Risk Assessment; SA-8 Security and Privacy Engineering Principles; SC-7 Boundary Protection | Categorisation, assessment and engineered boundaries |
| MITRE ATT&CK for ICS | TA0105 Impact: T0880, T0879, T0827, T0831, T0837 | Physical consequence scenarios |
| UK regulation | HSE OG86 Edition 2; NCSC Cyber Assessment Framework 4.0, objective A Managing security risk | Major accident hazard sites and operators of essential services |
Decision checklist
- Does the system, directly or through a dependency, affect a physical process or essential service? If yes, a cyber-physical assessment is required.
- Is there one consequence scale covering people, environment, plant, service and money, signed by risk and process safety?
- Are zones rated on unmitigated consequence before controls are credited?
- Has every High scenario been through cyber PHA, and the worst through CCE?
- Does each High scenario keep at least one safeguard that works under network compromise?
- Has each proposed control been tested for safety side effects and given a rollback?
- Is reassessment tied to management of change?
Practitioner checklist
- Adopt a shared consequence scale using the NIST SP 800-82 Rev. 3 impact categories as a starting point.
- Register IT systems whose loss forces an operational shutdown.
- Partition control systems into ISA/IEC 62443 zones and conduits and assign SL-T.
- Add cyber scenarios to the hazard register through a joint cyber PHA.
- Keep safety instrumented systems separate from control networks and check that separation holds.
- Credit mechanical and hard-wired safeguards; do not credit layers that share an attack path.
- Pre-agree which OT assets may be isolated during an incident and who decides.
- Rate OT access accounts by the consequence of the zone they reach.
Standards and references
- NIST: SP 800-82 Rev. 3 Guide to Operational Technology (OT) Security
- ISA: ISA/IEC 62443 Series of Standards
- HSE: OG86 Cyber Security for Industrial Automation and Control Systems
- Idaho National Laboratory: Consequence-driven Cyber-informed Engineering
- Idaho National Laboratory: Cyber-Informed Engineering
- NIST: SP 800-30 Rev. 1 Guide for Conducting Risk Assessments
- NCSC: Cyber Assessment Framework
- MITRE ATT&CK: Loss of Safety
Related NHI Mgmt Group resources: OT Security Guide · Top 10 OT Security Risks · IEC 62443-3-2 OT Risk Assessment Guide · Consequence-driven OT Risk (CCE) Guide