Dams and hydropower plants turn a cyber compromise into a physical event, because the same control systems that schedule generation also open spillway gates, move penstock valves and hold back a reservoir. This guide explains how the United States dams sector frames that risk, what the Federal Energy Regulatory Commission (FERC) expects from licensed hydropower projects under Section 9.0 of its security programme, how the CISA dams sector maturity model and framework guidance fit together, and which controls matter most for gate control, remote operation and the machine identities that run them.
It is written for OT security engineers, dam safety and operations managers, and the identity and network teams who support them. It does not repeat the general utility material in our Water and Wastewater Cybersecurity Guide; it focuses on what is specific to water retaining structures and generation.
Key takeaways
- CISA is the Sector Risk Management Agency for the dams sector, which covers dams, navigation locks, levees, hydropower projects, dikes, hurricane barriers and tailings and industrial waste impoundments.
- FERC's Security Program for Hydropower Projects puts licensed dams into security groups and, through Section 9.0, decides which dams must apply baseline or enhanced cyber measures based on remote operation and consequence.
- Section 9.0 is aimed at two consequences: unintentional release of all or part of the reservoir, and non-operation of a licensed facility. Plan your controls around those two outcomes.
- FERC published a draft revision of Section 9.0 for comment in April 2026 (docket AD26-6-000). Track the final text before you rebuild your programme around the 2016 wording.
- The CISA Dams-C2M2 and the Dams Sector Cybersecurity Framework Implementation Guidance are voluntary self-assessment tools. They tell you how mature you are, not which gate controller to isolate first.
- Remote and third-party access, flat networks between business and control systems, and unmanaged service and vendor accounts are the recurring weak points the sector material names.
- A safe manual fallback for gate operation, tested with the emergency action plan, is a cyber control as much as a dam safety one.
Why dams are a distinct OT security problem
Most OT environments can be shut down to a safe state. A dam cannot simply be switched off: water keeps arriving, and the safe state depends on reservoir level, inflow forecasts and downstream conditions. A control action that is harmless in one season can be dangerous in another. That is why cyber risk at a dam is assessed in terms of consequence to people downstream, not only in terms of system availability.
CISA's dams sector fact sheet sets out the scale. It counts more than 91,000 dams in the National Inventory of Dams database, more than 100,000 dams across the United States and Puerto Rico, and nearly 6,900 levee systems totalling 24,500 miles. The sector helps protect more than 43 percent of the US population from flooding and generates about 60 percent of electricity in the Pacific Northwest. Ownership is split across a large and diverse set of public and private entities, and oversight is distributed across federal, state and local bodies.
The same fact sheet lists the cyber hazards the sector worries about: attacks on inadequate controls, outdated patches and unknown vulnerabilities, social engineering to obtain operator credentials, and insider threats. It also names an ageing workforce and loss of institutional knowledge as a risk. That last point matters for security: when the one engineer who understands a legacy gate PLC retires, undocumented remote access paths and shared passwords tend to stay behind.
In MITRE ATT&CK for ICS terms, the impacts that matter most are Manipulation of Control (T0831) and Damage to Property (T0879), and the most common ways in are External Remote Services (T0822) and Remote Services (T0886). Device Restart/Shutdown (T0816) is the inhibit response technique to think about when protection relays or gate controllers can be rebooted remotely.
Who sets the rules: CISA, FERC and NERC
Three bodies shape cyber expectations for US dams and hydropower. Knowing which applies to which asset avoids both gaps and duplicated audits.
| Body | Role | What it gives you |
|---|---|---|
| CISA | Sector Risk Management Agency for dams | Voluntary guidance: Dams-C2M2 and its implementation guide, the Dams Sector Cybersecurity Framework Implementation Guidance, security guidelines, training courses and a tabletop exercise toolbox |
| FERC Division of Dam Safety and Inspections | Regulator for licensed non-federal hydropower projects | Security Program for Hydropower Projects, including security group classification and Section 9.0 on computer security and SCADA, checked during inspections |
| NERC | Reliability standards for the bulk electric system | CIP standards that apply to generation assets in scope; FERC guidance says an asset under both FERC dam safety and NERC CIP must meet NERC CIP |
FERC's guidance is explicit that its dam safety interest focuses on remote operations that could affect water retaining structures (the dam, spillway gates and releases) and power generation. It states that this interest does not extend into the corporate business network, unless access controls between the networks are missing or the business network can control operations. In practice that means the boundary between business and control networks is the first thing an inspector will want to understand.
Where a powerhouse is also a NERC CIP asset, reference the applicable CIP standards in the security plan and keep compliance inspection results, deficiencies and corrective actions ready for review. Our NERC CIP-002 BES Cyber System Categorisation Guide covers that categorisation step.
FERC security groups and what each must produce
FERC's Security Program for Hydropower Projects (Revision 3, with a Revision 3A cover dated 30 March 2016) applies to FERC licensees and exemptees. It sorts dams into three security groups based on potential consequences, vulnerability and likelihood of attack. The criteria for Groups 1 and 2 are not published in the open document; they are given to licensees during inspection. Any FERC dam that does not meet Group 1 or 2 criteria is Group 3.
| Requirement | Group 1 | Group 2 | Group 3 |
|---|---|---|---|
| Security assessment | Included in the vulnerability assessment | Required | Highly recommended |
| Vulnerability assessment | Required | Not required | Not required |
| Security plan | Required | Required | Highly recommended |
| Internal emergency response | Required | Required | Not required |
| Rapid recovery | Required | Not required | Not required |
| Annual certification letter | Required | Required | Not required |
Security plans for Groups 1 and 2 must be available on site, or at a control centre for unstaffed dams, and updated at least annually. Group 1 plans must be exercised at least every five years at drill level or higher. The annual certification letter goes to the FERC Regional Engineer by 31 December and must address cyber compliance. Cyber and SCADA measures can sit inside the security plan or in a separate cyber and SCADA security plan.
One detail is easy to miss. A Group 3 dam that is remotely operated and interconnected with operational or critical cyber assets of a Group 1 or Group 2 dam falls under Section 9.0. A small unstaffed dam on the same SCADA network as a large one inherits its obligations.
Section 9.0: deciding which cyber measures apply
Section 9.0, titled Computer Security and SCADA, took effect on 1 January 2016. It runs as a three step determination using FERC's Hydro Cyber/SCADA Security Checklist (Form 3).
Step 1: remote operation screening
Every Group 1 and 2 dam answers the first four questions of Form 3 and discusses them with the project engineer at the next operation inspection. A yes to any of these means the licensee must go on to evaluate consequences:
- Automated or remote (off site) control of data acquisition, such as critical instrumentation.
- Automated or remote control of power generation data or controls.
- Automated or remote control of water management data, or direct control of water retention features.
- Computer system interconnection to other dams, including virtual interconnections.
Step 2: consequence determination
The licensee considers whether compromise could release the reservoir, cause loss of generation, cause loss of other missions such as navigation or water supply, lead to all gates being fully open with no remediation for 48 hours, or trigger cascading failures that could cause dam failure.
Step 3: criticality thresholds
The asset is critical if any consequence exceeds FERC's thresholds, which include a population at risk of more than 60 people within 3 miles, more than 800 within 60 miles, more than 12,500 in total from a reservoir release, total economic losses above 300 million dollars, or disruption of essential services beyond a municipal wide disruption. For powerhouses, installed capacity per cyber asset drives classification: 1,500 MW or more is critical, 100 MW up to 1,500 MW is operational, and under 100 MW is non-critical. Any unit with black start capability is operational regardless of size.
The outcome is one of three classes. Non-critical assets (isolated from remote monitoring and control) are re-evaluated annually. Operational assets complete Form 3 questions 5 to 33, provide a plan and schedule for any negative answer, and implement baseline measures. Critical assets do the same and add enhanced measures. Interconnected facilities carry the same obligations.
FERC staff issued a draft revision of Section 9.0 on 17 April 2026, published in the Federal Register on 22 April 2026 under docket AD26-6-000. The notice says the revision aims to modernise the existing cyber guidance and proposes updated definitions, revised applicability criteria and revised technical measures. The comment period closed on 18 May 2026. Status as of 19 November 2026: check FERC's docket for whether a final version has been issued before relying on the 2016 thresholds above.
Baseline and enhanced controls for gate and generation systems
FERC defines control systems as SCADA, process control systems and distributed control systems, and for this guidance SCADA also covers remote operation of spillway gates, penstocks and similar features. The baseline measures in Table 9.3a apply to every cyber asset in scope:
- Inventory and criticality. Keep an accurate inventory of cyber assets and systems, and reassess criticality at intervals of no more than 12 months and whenever assets are added. Our OT Asset Visibility Guide covers passive discovery that will not disturb gate controllers.
- Segregation. Separate the control system network from the business network and the internet with firewalls and other protections, wired and wireless, and use control system computers only for approved activities.
- Connections review. Monitor and review network connections, including remote and third party connections, at intervals of no more than 18 months. Reassess wireless before it is deployed.
- Lifecycle. Build security into design and change, document configuration, change tracking and patching policies, and document secure disposal of equipment and media.
- Restoration. Be able to restore control systems in a timely way, and test the restoration and recovery plan annually.
- Detection and response. Establish procedures for intrusion monitoring, detection, incident handling and reporting.
- Training and roles. Form a cross functional cyber security team spanning operations, IT, business, outsourcers and contractors, and provide annual awareness training before granting access.
Enhanced measures in Table 9.3b add restricted physical and logical access (locked facilities, passwords, secured gateways, access control lists, authenticators, separation of duties and least privilege), a risk assessment before using wireless, and control system vulnerability assessments at intervals of no more than 12 months, in non-production environments where appropriate.
For a practical zoning model, the gate control PLCs, protection relays and governor controls belong in their own zones, with the plant historian and engineering workstations in a separate supervisory zone and a demilitarised zone in front of any business or vendor connection. Our OT Network Segmentation, Purdue Model and IEC 62443 Zones and Conduits Guide walks through the conduit design. The joint CISA, FBI, EPA and DOE Primary Mitigations to Reduce Cyber Threats to Operational Technology is a short companion list to prioritise from.
Remote access, vendors and machine identities
Unstaffed dams and centralised control rooms are the reason remote access exists in this sector, and also the reason it is the main exposure. FERC's Form 3 asks about vendor and third party remote access, the access controls on it, and whether that activity is logged and reviewed at least weekly. It also asks whether controls allow logging, monitoring, detection and isolation of anomalous events, and how often they are reviewed.
The CISA framework guidance maps remote access to the NIST Cybersecurity Framework subcategory for managing remote access, with an example of encrypted VPN access plus logging and monitoring, and to the subcategory for approving, logging and controlling remote maintenance. It also lists basic steps: change factory set passwords, apply validated patches, lock down unused ports, and enforce lockout and access revocation policies.
From an identity point of view, a dam's control estate holds several kinds of non-human identity that rarely appear in the corporate identity platform:
- Service accounts used by SCADA servers to poll remote terminal units and PLCs.
- Historian and data diode accounts that push telemetry to business systems or to river forecasting partners.
- Vendor support accounts and jump host credentials for turbine, governor and gate control suppliers.
- Shared operator logins on HMIs at the control centre and at the dam.
- Certificates and keys on VPN concentrators and secure gateways.
Give each of these an owner, a documented purpose and a review date. Vendor access should be brokered, time limited and recorded, not an always-on VPN tunnel. Where the control domain uses Active Directory, monitor its privileged and service accounts as described in our D3-DAM Domain Account Monitoring page. The OT Remote Access Guide covers broker patterns in more depth.
Manual fallback, emergency action plans and recovery
FERC requires internal emergency response for Group 1 and 2 dams and says it must cover coordination between security notification and the emergency action plan. Rapid recovery is required for Group 1, and for Group 1 cyber assets FERC states that compliance with NERC CIP-009-1 meets the recovery requirement.
For cyber planning, three questions need tested answers:
- Can the gates be operated locally if SCADA is untrusted? Document the local or manual operating procedure for each gate, who is qualified to do it, how long it takes to get them on site, and how operators will know the true gate position and reservoir level if displays may be falsified.
- When do you disconnect? Agree in advance who can order remote links cut, and what the dam then runs on. Disconnecting a remote site with no staff on hand may be riskier than staying connected; the decision needs dam safety and operations input, not only security.
- How do you rebuild? Keep offline, tested backups of PLC logic, HMI projects, historian configuration and network device configurations. FERC Form 3 asks how often backups are tested.
CISA's dams sector resources include a Dams Sector Tabletop Exercise Toolbox and an information sharing drill. Our OT Incident Response Guide covers OT evidence handling and the order of recovery.
Using Dams-C2M2 and the CSF guidance to measure maturity
CISA's Dams Sector Cybersecurity Capability Maturity Model (Dams-C2M2) Implementation Guide, version 2.0, was published in October 2022. It is based on the Department of Energy C2M2 and is a self-evaluation tool for a single function, with operation of facility floodgates given as an example. The guide says it is not a regulatory framework and is not designed to issue a grade.
The model has ten domains: asset, change and configuration management; threat and vulnerability management; risk management; identity and access management; situational awareness; event and incident response, continuity of operations and service restoration; third party risk management; workforce management; cybersecurity architecture; and cybersecurity programme management. Practices are grouped into maturity indicator levels MIL0 to MIL3. To reach a level, all practices at that level and below must be complete, and the target level should reflect business objectives rather than always being the highest.
The guide runs as five steps: prepare, evaluate in a facilitated workshop, analyse gaps, prioritise and plan, then implement and re-evaluate. It includes worksheets and a gap mitigation plan template.
The separate Dams Sector Cybersecurity Framework Implementation Guidance, developed by CISA with the sector and government coordinating councils, applies the NIST Cybersecurity Framework through seven steps: prioritise and scope, orient, create a current profile, conduct a risk assessment, create a target profile, analyse and prioritise gaps, and implement an action plan. It names CISA's Cybersecurity Evaluation Tool (CSET) for assessing control system and IT security practices against recognised standards.
A sensible approach is to scope one C2M2 evaluation to "remote operation of spillway gates" and another to "generation dispatch", then feed the gaps into the FERC plan and schedule for Form 3 negative answers. That keeps the voluntary and regulatory tracks pointed at the same work. For a formal OT risk method, see our IEC 62443-3-2 OT Risk Assessment Guide.
Common failure patterns
- Treating a small dam as out of scope while it shares a SCADA network with a Group 1 dam. Interconnection pulls it into Section 9.0.
- Assuming the business network does not matter. FERC's interest extends into the corporate network when access controls between networks are missing or business systems can control operations.
- Permanent vendor tunnels to turbine or gate control suppliers, with shared credentials and no weekly review of activity.
- A recovery plan that assumes SCADA is trustworthy. If operators cannot verify gate position independently, a manipulated display can lead to wrong manual decisions.
- Annual certification without evidence. Signing the letter while connection reviews, backup tests and criticality reassessments are overdue.
- Running C2M2 once and filing it. The model expects re-evaluation when conditions change, such as a new remote site or vendor.
- Planning only around the 2016 text while a revised Section 9.0 is in progress.
Practitioner checklist
- Confirm the FERC security group of each dam and list every Group 3 site interconnected with a Group 1 or 2 site.
- Complete Form 3 questions 1 to 4 for each site and record the consequence determination and resulting class.
- Maintain an inventory of cyber assets, including gate PLCs, RTUs, protection relays, HMIs, historians and network devices, and reassess criticality at least every 12 months.
- Separate the control network from business systems and the internet, and document every conduit between them.
- Review all remote and third party connections at least every 18 months, and log and review vendor remote activity at least weekly.
- Assign an owner and review date to every service, vendor and shared account in the control environment.
- Change factory default passwords and close unused ports on field devices.
- Document and drill local or manual gate operation with the emergency action plan.
- Test the control system restoration plan and backups annually.
- Run a Dams-C2M2 evaluation for gate operation and feed the gaps into your FERC plan and schedule.
- Track FERC docket AD26-6-000 for the final revised Section 9.0.
Standards and references
- FERC: Security Program for Hydropower Projects, Revision 3A, including Section 9.0 Computer Security and SCADA
- FERC: Notice of draft revised Section 9.0 guidance, docket AD26-6-000 (Federal Register, April 2026)
- CISA: Dams Sector Risk Management Agency fact sheet (2024)
- CISA: Dams Sector C2M2 Implementation Guide, version 2.0 (2022)
- CISA: Dams Sector Cybersecurity Framework Implementation Guidance
- CISA, FBI, EPA and DOE: Primary Mitigations to Reduce Cyber Threats to Operational Technology
- NIST: SP 800-82 Rev. 3, Guide to Operational Technology (OT) Security
- MITRE ATT&CK: ICS Matrix
Related NHI Mgmt Group resources: Water and Wastewater Cybersecurity Guide · T0879 Damage to Property · OT Remote Access Guide · OT Incident Response Guide