ICCP links carry the real-time measurements, schedules and sometimes control requests that neighbouring utilities, reliability coordinators and market operators rely on, yet the base protocol authenticates nothing and encrypts nothing. Security has to come from Secure ICCP profiles, a well run certificate service between organisations, tight bilateral tables and a network design that treats every peer as untrusted. This guide covers how ICCP works from a security point of view, the threats to inter-control-centre links, how Secure ICCP and IEC 62351-4 apply, certificate lifecycle between peers, NERC CIP obligations, and monitoring for anomalous associations. It is written for utility OT security engineers, EMS and SCADA engineers and the compliance teams who evidence CIP-012. For the series of power system security standards as a whole, see the IEC 62351 Power System Communications Security Guide; this page applies it to ICCP and does not repeat it.

Key takeaways

  • Plain ICCP is an unprotected protocol. PNNL's Secure ICCP final report describes it as vulnerable to interception, alteration, spoofing and eavesdropping unless security is added.
  • The bilateral table is your access control list. It defines which data objects each peer may read or write; it is only as good as the review process behind it.
  • Secure ICCP means TLS plus MMS association authentication. IEC 62351-4 defines a transport profile (TLS) and an application security profile for the MMS handshake, and its 2018 edition adds end-to-end security.
  • Certificates between organisations are the hard part. Agree the CA model, distinguished names, renewal and revocation with each peer in writing, and test renewal before expiry.
  • CIP-012-2 now covers availability. As of 1 July 2026 entities must protect confidentiality, integrity and availability of real-time data between Control Centres and plan link recovery.

What ICCP and TASE.2 are

ICCP (Inter-Control Center Communications Protocol) is the common name for TASE.2, Telecontrol Application Service Element 2, defined in the IEC 60870-6 series. The current services and protocol part, IEC 60870-6-503:2014 (edition 3.0), describes a method of exchanging time-critical control centre data over wide and local area networks using an ISO protocol stack. TASE.2 runs over MMS (Manufacturing Message Specification), which in practice is carried over TCP using ISO transport (RFC 1006, TCP port 102).

Each ICCP server exposes a Virtual Control Centre (VCC) to its peers. A client opens an MMS association, identified by AP titles and AE qualifiers, then reads data values, sets up data sets and transfer sets so the server reports changes or periodic values, and in some deployments sends information messages or device control requests. Functions are grouped into conformance blocks:

BlockFunctionSecurity relevance
1Basic services (periodic system data)Mandatory; reading the real-time values operators see
2Extended data set condition monitoringReport by exception; spoofed or suppressed reports change what peers see
3Block data transferBulk transfer efficiency; same integrity concerns as block 1
4Information messagesFree text or file style messages between operators; social engineering and data leakage path
5Device control (including select before operate)Highest consequence: lets a peer request operation of a device; enable only where an agreement needs it
6 to 9Program control, event reporting, additional user objects, time seriesMade out of scope in IEC 60870-6-503 edition 3; disable if a product still offers them

Most products implement blocks 1, 2 and 5, with block 3 or 4 where needed. The narrower the block set agreed with a peer, the smaller the attack surface.

Bilateral agreements and bilateral tables

IEC 60870-6-503 treats access control through bilateral agreements and bilateral tables. The agreement is the business and operational document between two organisations; the bilateral table is its machine form on each server, listing the data objects, data sets and devices a peer may access and with what rights. The table format is outside the standard and is product specific, which is why errors creep in during manual edits.

  • Least privilege: list objects explicitly. Avoid wildcard or "all points" entries, and give read-only access unless the agreement names a control use case.
  • Device control: if block 5 is needed, list each controllable point separately and require select before operate where the product supports it.
  • Matching entries: both sides must configure matching entries, so changes need a joint change record and a test window.
  • Peer identity: bind the table to the authenticated peer identity (certificate distinguished name in Secure ICCP), not only to IP address or AP title, which can be spoofed.
  • Review: reconcile the table against the signed agreement at least annually and whenever a peer, data point or contact changes.

ICCP links cross organisational boundaries, often over leased WAN circuits or shared utility networks. That means you inherit the security of every peer and every carrier on the path. The table maps the main threats to ATT&CK for ICS techniques and the controls that address them.

ThreatATT&CK for ICSPrimary controls
Interception or alteration of values in transitT0830 Adversary-in-the-MiddleSecure ICCP (TLS with mutual certificate authentication), or IPsec or link encryption where TLS is not yet possible
False values shown to operatorsT0832 Manipulation of ViewIntegrity protection, state estimator plausibility checks, cross-checks against other sources
Unauthorised control requests through block 5T0831 Manipulation of ControlBlock 5 disabled by default, per-point bilateral entries, select before operate, operator confirmation
Compromise of a peer used as a stepping stoneT0866 Exploitation of Remote ServicesICCP servers in a DMZ, no other protocols across the link, patched ICCP stacks
Abuse of ICCP as an allowed channelT0869 Standard Application Layer ProtocolProtocol aware monitoring, firewall rules limited to known peer addresses and ports
Loss of data flow or link floodingT0814 Denial of ServiceDiverse paths, rate limiting connection attempts, carrier SLAs, recovery plans (CIP-012-2 R1.2 and R1.3)

Sandia's Secure ICCP integration report also notes that encryption does not hide traffic metadata: an observer can still see which centres talk, when and how much. Treat link addressing and topology as sensitive information.

Secure ICCP and IEC 62351

Secure ICCP is the profile of ICCP that uses the IEC 62351-4 security mechanisms. IEC 62351-4:2018 extends the original IEC TS 62351-4:2007 and defines two modes: a compatibility mode that interoperates with existing implementations, and a native mode with extended capabilities. It is built from three layers:

ProfileWhat it doesPractical notes for ICCP
T-profile (transport)TLS protection of the ISO transport over TCP, with IEC 62351-3 as a normative reference for TLS useMutual authentication: both servers present certificates; agree cipher suites and TLS versions with each peer
A-security-profile (application)Authentication during the MMS association handshakeAuthenticates the ICCP node at the MMS layer, separate from the TLS session
E2E security (native mode)Integrity, authentication and shared key management for handshake and data transfer, through intermediate entitiesRelevant where gateways or protocol converters terminate TLS; check product support before planning on it

The IEC 62351-4:2018 scope notes that existing ICCP implementations depend on the 2007 T-profile and A-security-profile, carried forward for interoperability. In procurement and peer agreements, name the edition and mode you require, and ask each vendor for the conformance statement that lists which profiles, TLS versions and cipher suites the product supports. IEC 62351 parts are paywalled IEC publications; use the titles and editions in specifications and buy the texts for the engineers who configure them.

When Secure ICCP is not yet possible: Sandia's report lists IPsec and data link encryption as ways to protect standard ICCP. These protect the path between gateways but do not authenticate the ICCP application itself, so keep bilateral table restrictions strict and plan migration. For a broader view of mutual TLS design, see the mTLS Guide.

Certificates and key management

Every Secure ICCP link is a machine to machine trust relationship between two organisations. ICCP server certificates are non-human identities and need the same ownership, inventory and lifecycle discipline as any other workload credential. The OT and ICS Identity and Access Guide covers the wider OT identity picture.

  • CA model: Sandia recommends a flat hierarchy within one company and a tiered hierarchy across companies, and advises against public internet CAs for control networks because their revocation lists are large and irrelevant and response to revocation is slower. Most utilities use a private CA dedicated to OT. See Private PKI vs Public PKI.
  • Policy by name: bind access to the peer's distinguished name, not to a specific certificate, so renewal does not require reconfiguring every table.
  • Separate certificates by purpose: Sandia recommends distinct certificates for TLS and MMS authentication rather than one certificate for everything.
  • Revocation in long sessions: ICCP associations stay up for weeks. A TLS session established before a certificate was revoked will not recheck it, so configure periodic renegotiation or reconnection, and renegotiate when a new CRL arrives, as Sandia recommends.
  • Key protection: keep private keys in an HSM or the product's protected key store where available, with export disabled.

Peer certificate lifecycle should be written into the bilateral agreement:

  1. Enrol: each side issues its own server certificate from its CA and exchanges CA certificates (not private keys) with the peer over an authenticated channel, verifying fingerprints by a second route.
  2. Record: add each certificate to an inventory with owner, peer, expiry, CA and the link it serves. The Certificate Inventory Register Template gives a format.
  3. Renew: agree a notice period (for example 60 days) and a joint test window; renew before expiry, test on a standby link, then switch.
  4. Revoke: agree how each side publishes revocation (CRL distribution point or OCSP reachable from the peer DMZ) and the contact route for emergency revocation.
  5. Roll back: keep the previous certificate valid until the new one is proven on both sides, so a failed renewal can be reversed without losing data flow.

Certificate expiry is the most common cause of a Secure ICCP outage. The Certificate Expiry Outages and 47-Day TLS Certificates Guide covers monitoring patterns that apply here.

NERC CIP relevance

For North American entities, ICCP links fall under several CIP standards. See the NERC CIP Guide for the whole family.

StandardRequirementWhat it means for ICCP
CIP-012-2R1.1 methods to mitigate unauthorised disclosure and modification of real-time assessment and monitoring data between Control CentresSecure ICCP or equivalent encryption and integrity on every applicable link
CIP-012-2R1.2 and R1.3 methods to mitigate loss of the ability to communicate, and to initiate recovery of linksDiverse paths, backup links and documented restoration steps
CIP-012-2R1.4 where the methods are implemented; R1.5 each entity's responsibilities when Control Centres belong to different entitiesDemarcation points and responsibilities written into the bilateral agreement
CIP-005-7R1.1 to R1.3 ESP, EAP and inbound and outbound permissions with a reason, deny by defaultFirewall rules for each ICCP peer, documented with the business reason
CIP-005-7R1.5 detect known or suspected malicious communications at EAPs for high impact systems and medium impact systems at Control CentresIDS or protocol aware monitoring at the ICCP boundary

FERC approved CIP-012-2 on 23 May 2024, and Texas RE states its effective date as 1 July 2026. CIP-012-2 excludes oral communications and has an exemption for Control Centres sending data only about co-located generation or transmission facilities; check the exact applicability text for your sites. Regional obligations outside the US differ; the Electric Utility Cybersecurity Programme Guide covers the wider regulatory context.

Outside CIP, the same controls map to general frameworks:

ICCP controlNIST SP 800-53 Rev 5NIST CSF 2.0
Secure ICCP encryption and integritySC-8 Transmission Confidentiality and Integrity; SC-23 Session AuthenticityPR.DS-02
Mutual peer authenticationIA-3 Device Identification and AuthenticationPR.AA-03
Peer certificates and keysSC-12 Cryptographic Key Establishment and Management; SC-17 Public Key Infrastructure CertificatesPR.DS-02
Bilateral tables and DMZ conduitsAC-4 Information Flow Enforcement; SC-7 Boundary ProtectionPR.AA-03
Association monitoringSI-4 System Monitoring; AU-6 Audit Record Review, Analysis, and ReportingDE.CM-01
Diverse links and recoveryCP-8 Telecommunications ServicesPR.DS-02

Network architecture and monitoring

  • ICCP in a DMZ: place ICCP servers in a dedicated DMZ between the EMS network and the WAN, so peers never reach EMS hosts directly. Replicate data from the EMS to the ICCP server rather than exposing EMS databases. See OT Network Segmentation, Purdue Model and IEC 62443 Zones and Conduits and the IEC 62443 Guide.
  • One conduit per peer: firewall rules allow only the peer's ICCP server addresses and agreed ports; no management, file transfer or remote access shares the ICCP path.
  • Redundancy: primary and backup ICCP servers and diverse carriers support CIP-012-2 availability; test failover at least twice a year.
  • Logging: collect ICCP server logs (association start and stop, authentication failures, bilateral table rejects, certificate errors), firewall logs and TLS handshake failures into the SOC.

Monitoring for anomalous associations works because ICCP traffic is highly predictable. Baseline each peer and alert on deviation:

SignalWhat it can indicateResponse
Association from an unknown address, AP title or certificate DNSpoofed peer or misconfigurationBlock, contact peer by known route
Authentication or certificate validation failuresExpired certificate, wrong CA, or impersonation attemptCheck inventory and peer change records
Reads or writes rejected by the bilateral tablePeer reconnaissance or a stale peer configurationReview with the peer; escalate if repeated
Device control (block 5) requests outside agreed points or timesPossible unauthorised control attemptImmediate operator and SOC escalation
Unencrypted ICCP where Secure ICCP is agreedDowngrade or fallback configurationTreat as a security incident and a CIP-012 issue
Association churn, connection floods or data gapsDenial of service, carrier fault or peer outageInvoke link recovery plan

Protocol aware OT monitoring can parse MMS and TASE.2; see the OT Network Security Monitoring Guide.

Metrics that show the programme works:

  • Share of ICCP links running Secure ICCP with mutual authentication (target 100% of CIP-012 links).
  • Certificates expiring within 60 days without a scheduled renewal (target zero).
  • Bilateral tables reconciled with their agreement in the last 12 months.
  • Peers with block 5 enabled, and the number of controllable points per peer.
  • Mean time to restore an ICCP link in failover tests.

Common failure patterns

  • Secure ICCP licensed but not enabled: products ship with the capability, but links stay plain because peers never agreed certificates. Set a migration date in every agreement.
  • Wildcard bilateral tables: "all points readable" entries copied from a test configuration expose far more than the agreement covers.
  • Certificate expiry outages: no shared renewal process, so a certificate lapses and the link drops, and teams fall back to unencrypted ICCP to restore data flow.
  • Revocation never checked: CRLs not reachable from the DMZ, or long sessions never renegotiated, so a revoked peer certificate keeps working.
  • Flat network behind the ICCP server: the ICCP server sits on the EMS network, so a compromised peer has a direct path to operations systems.
  • Responsibilities undefined: no CIP-012 R1.5 split between entities, so neither side monitors the shared link or owns recovery.

Practitioner checklist

  • Inventory every ICCP link: peer, servers, carriers, conformance blocks, Secure ICCP status and certificates.
  • Reconcile each bilateral table with its signed agreement; remove wildcards and unused points.
  • Disable block 5 unless a named operational use exists, and restrict it per point.
  • Agree Secure ICCP edition, mode, TLS versions and cipher suites with each peer, in writing.
  • Run a private OT CA, bind access to distinguished names and document renewal and revocation with each peer.
  • Place ICCP servers in a DMZ with one firewall conduit per peer and documented reasons (CIP-005 R1.3).
  • Send ICCP, TLS and firewall events to the SOC and alert on the anomalies in the monitoring table.
  • Test failover and link recovery and record the results as CIP-012-2 evidence.

Standards and references

Related NHI Mgmt Group resources: IEC 62351 Power System Communications Security Guide · NERC CIP Guide · DNP3 and DNP3 Secure Authentication Guide · Industrial Protocol Security Guide · Smart Grid Security Guide

PDF for subscribers

Take this guide with you

Every section, table and checklist in one PDF, with links to the sources and related guides. Subscribe to our weekly NHI & AI Identity Journal and we’ll email you a download link.

Free weekly newsletter

Subscribe to the NHI & AI Identity Journal

The latest on NHI and Agentic AI security – articles, research, breaches, news and events every week.

Bonus 33% off our NHI Course when you subscribe.

PDF Downloads for Newsletter Subscribers

Get the guide

Enter your details and we’ll email you a download link.

The full guide is free to read online. The PDF is a thank you for subscribing.

Fill in all fields marked * and tick both boxes to continue.