Radio links carry telemetry and control traffic across many OT estates, and anyone within range can listen, inject or jam without ever touching a cable or a fence. Utilities, water companies, oil and gas operators and manufacturers use licensed and unlicensed radio for SCADA telemetry to remote sites, wireless field instruments, plant Wi-Fi and backhaul. This guide covers the threats to those links, the native security options of common OT radio technologies, how to provision and rotate keys on field radios, how to protect firmware and configuration, and how to monitor for jamming and rogue transmitters. It is written for OT engineers and ICS security leads, stays vendor neutral and is purely defensive. Spectrum and equipment rules differ by country, so check local regulation before changing radio parameters.

Key takeaways

  • Treat every radio link as an untrusted network. NIST SP 800-82 Rev. 3 puts wireless devices in a separate segment behind a boundary protection device, used only where residual risk is low.
  • Encryption is not the same as authentication. Link encryption hides content, but you also need message integrity and device admission control so a rogue master or field device cannot inject commands.
  • Keys are the weak point in practice. Default, shared and never-rotated join keys and pre-shared keys are more common than broken cryptography; per-device keys and a tracked rotation process fix most of it.
  • Radio firmware is control system firmware. Accept only signed images, block downgrades, and treat remote firmware update features on radios as privileged functions.
  • Plan for jamming, because you cannot prevent it. Monitor link quality and spectrum, design fail-safe behaviour on loss of communications, and keep a fallback path for critical telemetry.

Where radio is used in OT

NIST SP 800-82 Rev. 3 describes radio frequencies, including broadcast, microwave and satellite, as ways to carry SCADA data between control centres and field sites. MITRE ATT&CK for ICS lists WirelessHART, Zigbee, WIA-FA and 700 MHz public safety spectrum as examples of wireless protocols found in cyber-physical environments. The table below summarises common technologies and their native security options; the right column is what to confirm with your vendor because implementations differ.

TechnologyTypical OT useNative security optionsConfirm with the vendor
WirelessHART (IEC 62591)Wireless field instruments in process plants128-bit AES always on; session, network and join keys; keyed message integrity check on every packet; security manager usually in the gateway; channel hoppingPer-device join keys (access control list), automatic key rotation, gateway hardening
LoRaWANLow-power sensors, metering, remote monitoringMandatory AES-128 authentication and encryption; separate network and application session keys; root keys held in a join server; over-the-air activation allows rekeyingUnique keys per device, secure element support, join server ownership, avoidance of nonce reuse
Plant Wi-Fi (IEEE 802.11)Mobile HMIs, handhelds, video, AGVsWPA3 with Protected Management Frames required for new certified devices; enterprise authentication with 802.1XWPA3 support on industrial clients, roaming performance, certificate handling
Licensed narrowband UHF/VHF SCADA radioTelemetry to RTUs at pump stations, substations, wellheadsVaries by product: some offer link encryption and radio authentication as options, many legacy deployments run in clear textWhether encryption is available, the algorithm and key length, and the throughput and latency impact
Point-to-point microwaveBackhaul between sites and control centresVaries by product: optional link-layer encryption on many current radiosEncryption option and its licensing, management interface protection
Private or public cellular (LTE/5G)Remote sites, mobile assets, backup pathsSIM-based network authentication and air-interface encryption provided by the networkPrivate APN, gateway hardening, end-to-end encryption above the radio layer

For protocol detail see the LoRaWAN Security Guide and the Cellular Router and Gateway Hardening Guide.

ThreatATT&CK for ICSDefensive controls
Eavesdropping on telemetry to learn the process and tag namesT0887 Wireless Sniffing; T0861 Point & Tag IdentificationLink encryption (M0808 Encrypt Network Traffic); minimise signal propagation (M0806)
Joining or impersonating a wireless network or deviceT0860 Wireless CompromiseDevice allowlisting, unique join keys, communication authenticity (M0802)
Sending commands as a fake master stationT0848 Rogue MasterAuthenticated protocols such as DNP3 Secure Authentication, message integrity, segmentation
Intercepting and altering traffic between master and outstationT0830 Adversary-in-the-MiddleIntegrity protection at link and application layers, key protection
Jamming or flooding the channelT0814 Denial of ServiceSpectrum monitoring, fail-safe design, alternative paths
Malicious firmware on radios or gatewaysT1693 Modify Firmware; T0800 Activate Firmware Update ModeCode signing (M0945), restricted update functions, audit (M0947)

MITRE's T0860 entry records a case where a modified remote control was used to change track settings on a city tram network, a reminder that unauthenticated radio control can have physical effects. See ICS T0860 Wireless Compromise and T0887 Wireless Sniffing.

NIST SP 800-82 Rev. 3 section 6.2.9 asks for encryption of wireless traffic without degrading operational performance, considering layer 2 encryption and hardware acceleration, and for wireless field networks to use standard, non-proprietary protocols, encrypt traffic between instruments and access points, and allowlist devices in the wireless device manager.

  • Turn on what the radio already has: many licensed SCADA radios and microwave links ship with encryption as an option that was never enabled. Enable it, test latency and throughput against polling cycles, and record the setting in the asset register.
  • Authenticate at the application layer too: radio encryption protects the hop, not the end-to-end conversation. Where the SCADA protocol supports it, use authentication above the radio, for example DNP3 Secure Authentication. See the DNP3 and DNP3 Secure Authentication Guide.
  • Use a cryptographic overlay for legacy radios: where a radio has no usable encryption, a bump-in-the-wire encryptor or VPN at each end can protect serial or IP traffic, provided the link has enough bandwidth and the latency fits the process.
  • Segment the radio network: terminate radio links in their own zone and conduit with a firewall or data diode in front of the control network, consistent with IEC 62443-3-3 SR 5.1 Network segmentation.
  • Plant Wi-Fi: use WPA3 with Protected Management Frames, enterprise authentication for people and certificates for devices, a dedicated SSID per zone, and separate access point segments.

Choosing an approach

SituationPreferred optionTrade-off
Radio supports native encryptionEnable it, plus application-layer authenticationPossible latency and throughput cost; test first
Legacy radio, no encryption, adequate bandwidthExternal encryptor or VPN at each endExtra devices to manage and patch
Legacy radio, low bandwidth, slow pollingApplication-layer authentication only, tight segmentation, monitoring; plan replacementContent remains readable over the air
Small utility with few remote sitesManaged private cellular with private APN and VPNDependence on the carrier

Key management for field radios

The FieldComm Group's WirelessHART security paper recommends random, strong join keys rather than defaults, unique per-device join keys in an access control list where possible, periodic rotation of any common join key with all devices online, and secure storage and distribution of keys. The LoRa Alliance stresses unique keys per device, never reusing nonces, root keys isolated in a join server and secure elements in devices. The same principles apply to licensed radios that use pre-shared keys. See IoT Device Certificates vs Pre-Shared Keys.

  1. Inventory keys: record every radio network, key type (join key, network key, link key, pre-shared key), where it is stored, who can read it and when it last changed. See the OT Asset Register Template.
  2. Replace defaults at commissioning: generate keys with a proper random source, never reuse a site key across sites, and never leave factory keys in service.
  3. Prefer per-device credentials: per-device join keys or certificates mean one stolen field device does not expose the whole network.
  4. Protect the key store: keep keys in a secrets manager or hardware security module on the engineering side, not in spreadsheets or configuration backups on shared drives. Restrict who can export them.
  5. Rotate on a schedule and on events: rotate shared keys periodically and when staff or contractors with access leave, a device is lost or stolen, or a configuration backup is exposed. Check every device is online before changing a shared key, so none is orphaned.
  6. Test and roll back: rotate first on a test network or a single site, confirm polling recovers, and keep the previous key available through a defined change window so you can revert if devices fail to rejoin.

Firmware and configuration integrity

Radios, gateways and access points run firmware that an attacker can modify to persist or disrupt communications. RFC 9019, the IETF's firmware update architecture for IoT (Informational, April 2021), requires devices to verify the author and integrity of firmware images through a signed manifest, and uses a sequence number so a device is not tricked into installing an older valid image with known vulnerabilities. See the IoT Secure Firmware Update Guide (SUIT, signed OTA).

  • Accept only signed firmware: confirm with the vendor that radios verify signatures before flashing, and that downgrade protection is on. Map this to IEC 62443-3-3 SR 3.4 Software and information integrity.
  • Control over-the-air updates: many radio systems can push firmware and configuration over the radio network itself. Restrict that function to named engineering workstations, require authentication, and log every use.
  • Verify before deployment: obtain images from the vendor's authenticated portal, check published hashes, and stage on a test radio first.
  • Baseline configuration: keep a known-good configuration per radio (frequency, power, encryption setting, allowlist) and compare regularly; an unexpected change in encryption or allowlist settings is a security event.
  • Protect management interfaces: disable unused web, Telnet or SNMP services, change default credentials, and reach management only from the engineering zone.

Monitoring for jamming and rogue transmitters

Intentional jamming is unlawful in many countries; in the United States, for example, the FCC states that using, marketing or selling jammers is prohibited with no exemption for businesses. Operators therefore detect and respond rather than counter-jam.

  • Link health telemetry: collect received signal strength, signal-to-noise ratio, packet error rate and retries from radios and gateways into the historian or SIEM, and alert on sudden changes across several sites.
  • Spectrum monitoring: for critical licensed links, periodic or continuous spectrum analysis at key sites helps tell interference from equipment faults.
  • Rogue device detection: alert on join attempts from unknown device IDs, new access points or SSIDs, and master-station traffic from unexpected addresses.
  • Survey before deployment: NIST SP 800-82 Rev. 3 recommends a wireless survey to choose antenna locations and power, which also reduces how far signals travel beyond the site (ATT&CK mitigation M0806).
  • Design for loss of communications: define what each RTU or PLC does when polling stops, keep a secondary path (for example cellular as backup to licensed radio) for critical telemetry, and rehearse manual operation.

Metrics

  • Share of radio links with encryption enabled and verified.
  • Share of field devices with unique keys or certificates.
  • Age of the oldest shared key in service against the rotation target.
  • Radios running signed, current firmware.
  • Mean time to detect and localise sustained interference.

Framework mapping

FrameworkReferences
IEC 62443-3-3SR 1.6 Wireless access management; SR 2.2 Wireless use control; SR 3.1 Communication integrity; SR 3.4 Software and information integrity; SR 4.3 Use of cryptography; SR 5.1 Network segmentation; SR 7.1 Denial of service protection
NIST SP 800-53 Rev. 5AC-18 Wireless Access; SC-40 Wireless Link Protection; SC-8 Transmission Confidentiality and Integrity; SC-12 Cryptographic Key Establishment and Management; SI-7 Software, Firmware, and Information Integrity
MITRE ATT&CK for ICST0860, T0887, T0848, T0830, T0814, T1693; mitigations M0802, M0806, M0808, M0945
NIST SP 800-82 Rev. 3Section 6.2.9 Wireless Communications

See the IEC 62443-3-3 and 4-2 Security Levels Guide. NIST has published an initial public draft of SP 800-82 Rev. 4 for comment (comments due 30 November 2026); Rev. 3 remains the final version as of November 2026.

Common failure patterns

  • Encryption available but off: radios bought with encryption capability, commissioned in clear text to simplify troubleshooting and never changed.
  • One key everywhere: the same join key or pre-shared key across every site, unchanged since commissioning.
  • Keys in configuration backups: radio configuration files containing keys stored on shared drives or laptops.
  • Radio network bridged straight into the control LAN: no firewall between the radio zone and SCADA servers.
  • No plan for loss of link: outstations behaving unpredictably when polling stops, discovered during an outage rather than a test.

Practitioner checklist

  • List every radio link, technology, frequency band and the zone it connects.
  • Enable native encryption and verify it on each link; record exceptions with a replacement date.
  • Add application-layer authentication where the SCADA protocol supports it.
  • Replace default and shared keys with unique keys per device or site; store them in a protected key store.
  • Set a rotation schedule and an event-driven rotation process, tested on one site first.
  • Confirm radios accept only signed firmware and restrict over-the-air update functions.
  • Terminate radio links in a separate zone behind a boundary device.
  • Collect link health metrics and alert on interference and unknown devices.
  • Define and rehearse fail-safe behaviour on loss of communications.

Standards and references

Related NHI Mgmt Group resources: Industrial IoT (IIoT) Security Guide · IEC 62443 Guide · Industrial Protocol Security Guide · GNSS Spoofing and Jamming Guide

PDF for subscribers

Take this guide with you

Every section, table and checklist in one PDF, with links to the sources and related guides. Subscribe to our weekly NHI & AI Identity Journal and we’ll email you a download link.

Free weekly newsletter

Subscribe to the NHI & AI Identity Journal

The latest on NHI and Agentic AI security – articles, research, breaches, news and events every week.

Bonus 33% off our NHI Course when you subscribe.

PDF Downloads for Newsletter Subscribers

Get the guide

Enter your details and we’ll email you a download link.

The full guide is free to read online. The PDF is a thank you for subscribing.

Fill in all fields marked * and tick both boxes to continue.