NERC CIP-005 decides how routable traffic and remote users reach high and medium impact BES Cyber Systems, and remote access, especially vendor access, is where auditors look hardest. The standard requires an Electronic Security Perimeter (ESP) around applicable Cyber Assets, identified Electronic Access Points (EAPs) with deny-by-default rules, an Intermediate System, encryption and multi-factor authentication for all Interactive Remote Access (IRA), and the ability to see and cut off vendor sessions. This guide walks through CIP-005-7 requirement by requirement, explains what changes with CIP-005-8, and sets out the evidence that holds up at audit. It is for utility OT security engineers, network teams and CIP compliance staff. For the whole CIP family, start with the NERC CIP Guide.
Status checked 27 November 2026: CIP-005-7 is the enforceable version in the United States, with an enforcement date of 1 October 2022. FERC Order No. 919 (rule effective 26 May 2026) approved CIP-005-8 as part of the virtualisation package; it becomes enforceable under NERC's implementation plan, described below.
Key takeaways
- Every routable connection needs a perimeter. R1 Part 1.1 requires applicable Cyber Assets connected by a routable protocol to sit inside a defined ESP, and Part 1.2 requires all External Routable Connectivity (ERC) to pass through an identified EAP.
- Every firewall rule needs a reason. Part 1.3 requires inbound and outbound permissions with a documented reason for each, and everything else denied by default.
- Remote users never connect directly. R2 requires an Intermediate System for all IRA, encryption that terminates at that Intermediate System, and multi-factor authentication for every IRA session.
- Vendor sessions must be visible and stoppable. Parts 2.4 and 2.5 require methods to determine and to disable active vendor remote access, covering both IRA and system-to-system access, and R3 extends this to EACMS and PACS.
- CIP-005-8 is approved but not yet enforceable. It adds Shared Cyber Infrastructure (SCI) and Management Interfaces to scope; plan the transition now, but you are audited against CIP-005-7 until the effective date.
Scope and applicability
CIP-005-7 applies to Balancing Authorities, Generator Operators, Generator Owners, Reliability Coordinators, Transmission Operators, Transmission Owners and, for specific UFLS or UVLS, Remedial Action Scheme, Transmission Protection System and Cranking Path facilities, Distribution Providers. Exempt are Cyber Assets at facilities regulated by the Canadian Nuclear Safety Commission, Cyber Assets associated with communication networks and data links between discrete ESPs, systems covered by US Nuclear Regulatory Commission rules at 10 C.F.R. 73.54, and Responsible Entities with no high or medium impact BES Cyber Systems. Categorisation under CIP-002 therefore decides what is in scope; see the NERC CIP-002 BES Cyber System Categorisation Guide. Low impact sites are handled through CIP-003 instead; see the NERC CIP-003-9 Low Impact BES Cyber Systems Guide.
Each part lists its own Applicable Systems, and the differences matter for design:
| Part | Requirement (paraphrased) | Applicable systems |
|---|---|---|
| R1.1 | Applicable Cyber Assets connected by a routable protocol reside within a defined ESP | High and medium impact BCS and their Protected Cyber Assets (PCA) |
| R1.2 | All ERC passes through an identified EAP | High and medium impact BCS with ERC and their PCA |
| R1.3 | Inbound and outbound permissions with documented reasons; deny all other access by default | EAPs for high and medium impact BCS |
| R1.4 | Authenticate dial-up connectivity where technically feasible | High and medium impact BCS with Dial-up Connectivity and their PCA |
| R1.5 | Methods to detect known or suspected malicious communications, inbound and outbound | EAPs for high impact BCS; EAPs for medium impact BCS at Control Centers |
| R2.1 | IRA uses an Intermediate System so the initiating asset never directly accesses an applicable Cyber Asset | High impact BCS and PCA; medium impact BCS with ERC and PCA |
| R2.2 | Encryption for all IRA sessions, terminating at an Intermediate System | As R2.1 |
| R2.3 | Multi-factor authentication for all IRA sessions | As R2.1 |
| R2.4 | Methods to determine active vendor remote access sessions, IRA and system-to-system | As R2.1 |
| R2.5 | Methods to disable active vendor remote access, IRA and system-to-system | As R2.1 |
| R3.1 | Methods to determine authenticated vendor-initiated remote connections | EACMS and PACS associated with high impact BCS, and with medium impact BCS with ERC |
| R3.2 | Methods to terminate those connections and control the ability to reconnect | As R3.1 |
R2 as a whole is qualified "where technically feasible". Where a part cannot be met, the Technical Feasibility Exception process applies; it is not a quiet opt-out, and each exception needs compensating measures and a record.
Electronic security perimeters
An ESP is a logical border, not a physical one. Part 1.1 asks for a list of every ESP and the uniquely identifiable Cyber Assets connected by routable protocol within each. In practice that list should match the CIP-002 BCS inventory and the CIP-010 baselines, and the three should be reconciled whenever any one changes.
- Design boundaries around function: a control centre ESP, a substation ESP per site and a generating unit ESP are common patterns. Communication links between discrete ESPs are exempt, which is why wide-area links between substations are usually outside scope, but the endpoints that terminate them are not.
- Remove ERC deliberately: a medium impact BCS without ERC falls outside most of R1.2, R1.3 and the whole of R2. Some entities reduce scope by replacing routable links with serial or by moving the routable boundary; weigh this against operational need and document the decision.
- Protected Cyber Assets count: any non-BCS device inside the ESP becomes a PCA and inherits obligations. Keep printers, engineering laptops and convenience devices out of the ESP unless they are needed.
- Align with segmentation practice: IEC 62443 zones and conduits map well onto ESPs and EAPs, which helps when the same plant is assessed against both. See the OT Network Segmentation, Purdue Model and IEC 62443 Zones and Conduits Guide.
Electronic access points
An EAP is the interface on a Cyber Asset that controls routable communication across the ESP, typically a firewall interface. The EAP device itself is an Electronic Access Control or Monitoring System (EACMS), so it carries CIP-004, CIP-007, CIP-010 and CIP-013 obligations of its own.
- Rule justification (R1.3): every permit rule needs a documented reason, inbound and outbound. "Vendor support" is not a reason; "historian replication from the named DMZ host to the control centre historian on the single documented TCP port, owner: OT operations" is. Auditors sample rules and ask for the reason and the owner.
- Deny by default: show the explicit or implicit deny at the end of each rule base, and review "any" objects, broad port ranges and stale rules on a cadence. CIP-010 Part 1.4 requires verifying that CIP-005 controls are not adversely affected after a change.
- Dial-up (R1.4): authenticate dial-up where technically feasible, for example call-back or modem authentication. Better still, retire the modem and record the removal.
- Malicious traffic detection (R1.5): for high impact EAPs and medium impact Control Center EAPs, document at least one method, such as an intrusion detection system or application layer firewall, and show it is running and reviewed. CIP-015-1 adds monitoring inside the ESP; see the NERC CIP-015 Internal Network Security Monitoring Guide.
Interactive remote access and intermediate systems
NERC defines IRA as user-initiated access by a person employing a remote access client or other remote access technology using a routable protocol, from outside the ESP. System-to-system traffic is not IRA, but vendor system-to-system access is still covered by Parts 2.4 and 2.5.
The three IRA controls
- Intermediate System (R2.1): the user's device terminates on a jump host or proxy outside the ESP, typically in a DMZ, and only the Intermediate System initiates the onward connection through the EAP. Evidence is an architecture diagram showing the path.
- Encryption (R2.2): the session must be encrypted from the initiating device to the Intermediate System. A remote access VPN or TLS-protected remote desktop gateway are common choices; document where the encryption starts and ends.
- Multi-factor authentication (R2.3): every IRA session, every time. Document the factors (for example a password plus a hardware token or a phishing-resistant authenticator) and where they are enforced: at the VPN, at the Intermediate System or both. Enforcing MFA at the Intermediate System as well as the VPN means a stolen VPN credential alone does not reach the ESP.
Hardening the Intermediate System
The Intermediate System is an EACMS and an attractive target, because it holds the only path into the ESP. Treat it as tier zero: no web browsing or email, no trust from the corporate Active Directory, local or dedicated directory accounts, application allowlisting, session recording where possible, and credentials for onward hops held in a vault rather than typed by users. A compromised jump host is an incident in its own right; see If your jump host and bastion is compromised.
| Design choice | Strength | What to watch |
|---|---|---|
| Entity-run jump host in a DMZ | Full control of configuration, logs and evidence | Patching, hardening and staffing fall on you; it is an EACMS |
| Privileged access platform with session proxy | Vaulted credentials, recording, approval workflows | The platform components that control ESP access become EACMS too; check CIP-013 procurement |
| Vendor-hosted or cloud remote access service | Fast to deploy across many sites | You must still evidence R2.1 to R2.5; confirm where encryption terminates and who can see sessions |
See the OT Remote Access Guide and the Remote Access Identity Guide for architecture options beyond CIP.
Vendor remote access
Parts 2.4 and 2.5 sit alongside the supply chain obligations in the NERC CIP-013 guide. They ask for two capabilities: knowing when a vendor is connected, and being able to stop it. Neither requires a particular product. The measures in the standard list examples such as logs, connection tables, rule hit counters, checks for open ports and vendor call-in controls with a second factor.
- Determine (R2.4): keep named vendor accounts so a session can be attributed to a person, and alert on vendor session start. For system-to-system vendor connections, such as a vendor's remote monitoring feed, watch the relevant EAP rule hits or connection table entries.
- Disable (R2.5): for IRA, disable at the Intermediate System (kill the session and the account); for system-to-system, disable at the EAP (drop the rule or connection). Write the steps into a runbook and test them, because the method has to work during an incident at 3 a.m.
- EACMS and PACS (R3): Part 3.1 requires methods to determine authenticated vendor-initiated remote connections to EACMS and PACS, and Part 3.2 requires methods to terminate them and control the ability to reconnect, with examples such as disabling accounts or tokens, restricting vendor IP addresses or physically disconnecting a cable.
- Approve before connect: the standard does not mandate approval workflows, but just-in-time vendor accounts that are disabled by default make R2.5 trivial to evidence and remove standing access. See the Vendor Privileged Access Management (VPAM) Guide and the OT Third-Party and Integrator Access Guide.
Where identity fits: shared vendor logins defeat R2.4 because sessions cannot be attributed, and they complicate CIP-004 revocation. Named accounts with MFA, a personnel risk assessment record and a contract link solve both. Service accounts used for system-to-system vendor feeds should be owned, inventoried and restricted to the specific EAP rules they need. See the NERC CIP-004 Guide: Personnel Risk Assessment, Training and Access Revocation.
What changes with CIP-005-8
FERC Order No. 919 approved eleven modified CIP standards, including CIP-005-8, with the rule effective 26 May 2026. NERC's implementation plan makes them effective on the later of 1 April 2026 or the first day of the first calendar quarter that is 24 months after the effective date of the order, which on that reading points to 1 July 2028, with optional early adoption at six, 12 or 18 months by notifying your Regional Entity. Confirm the date with your Regional Entity. The order also replaces "technical feasibility" with "per system capability" in a number of requirements and modifies glossary terms including Electronic Security Perimeter, Electronic Access Point and Interactive Remote Access.
The CIP-005-8 draft text balloted under Project 2016-02 in 2024 adds SCI supporting an Applicable System to the Applicable Systems of several parts, introduces a part limiting network accessibility to Management Interfaces (for example hypervisor or storage fabric management), and adds parts on Intermediate Systems not sharing CPU or memory with high or medium impact BCS and on routing communications from Intermediate Systems through an ESP. Check the final approved text before designing to these details, because part numbering changed between drafts. Virtualised substations and control centres should start mapping SCI now.
Evidence for audits
Retain evidence for each requirement for three calendar years, or longer until any mitigation is completed and approved. Build evidence as a by-product of operations rather than a pre-audit scramble.
| Part | Evidence auditors typically request | How to produce it continuously |
|---|---|---|
| R1.1, R1.2 | ESP list with Cyber Assets; network diagrams showing ERC paths and EAPs | Generate from the asset register and reconcile with CIP-002 and CIP-010 baselines quarterly |
| R1.3 | Rule sets with a documented reason per rule; deny-by-default | Store the reason in the rule comment and a rule register; export after each change |
| R1.4 | Process describing dial-up authentication, or proof of removal | Keep an inventory of modems with status |
| R1.5 | IDS or equivalent deployed at the EAP; alert review records | Ticket each alert review; keep sensor health reports |
| R2.1 to R2.3 | Architecture showing Intermediate System, encryption endpoints and MFA factors | Keep the design document under change control; sample authentication logs |
| R2.4, R2.5, R3 | Documented methods to see and disable vendor sessions; proof they work | Run a quarterly disable test and keep the record with timestamps |
Monitor and measure
- Rules with a documented reason: target 100 percent of permit rules on every EAP.
- IRA sessions through the Intermediate System with MFA: 100 percent; any direct connection found is a potential violation to investigate.
- Time to disable a vendor session: measured in quarterly tests, in minutes.
- Standing vendor accounts: count of vendor accounts enabled outside an approved window, trending to zero.
- ESP inventory drift: Cyber Assets found by network monitoring that are not on the ESP list.
Common failure patterns
- Rules with no reason or a vague one: legacy "any any" rules for commissioning that were never removed.
- Undocumented paths: a cellular modem on an RTU or a vendor-installed remote access tool that bypasses the EAP and Intermediate System.
- MFA only at the VPN: acceptable on paper if documented, but a split tunnel or a second path straight to the Intermediate System can leave sessions without MFA.
- Shared vendor accounts: sessions cannot be attributed, and revocation after a vendor engineer leaves is unreliable.
- Untested disable methods: the runbook names a console that only one person can operate.
- Intermediate System joined to the corporate domain: a corporate compromise then reaches the ESP's only door.
Framework mapping
| CIP-005-7 area | NIST SP 800-53 Rev. 5 | NIST CSF 2.0 |
|---|---|---|
| ESP and EAP (R1.1 to R1.3) | SC-7 Boundary Protection | PR.IR-01 |
| Malicious communications detection (R1.5) | SI-4 System Monitoring | DE.CM-01 |
| IRA, encryption, MFA (R2.1 to R2.3) | AC-17 Remote Access, SC-8, IA-2 | PR.AA-03 |
| Vendor session visibility and termination (R2.4, R2.5, R3) | AC-2 Account Management, AU-12 | PR.AA-05 |
Practitioner checklist
- Reconcile the ESP list against CIP-002 categorisation and CIP-010 baselines, and keep non-essential devices out of ESPs.
- Draw every ERC path and confirm each passes through an identified EAP; hunt for cellular modems and vendor tools.
- Give every EAP permit rule an owner and a specific documented reason, and review rule bases on a set cadence.
- Deploy and evidence malicious traffic detection at high impact and medium impact Control Center EAPs.
- Route all IRA through a hardened Intermediate System outside the corporate domain, with encryption to it and MFA on every session.
- Use named, just-in-time vendor accounts and test the disable method for IRA and system-to-system access every quarter.
- Extend vendor session visibility and termination to EACMS and PACS under R3.
- Map Shared Cyber Infrastructure and Management Interfaces now, and plan the CIP-005-8 move against the date confirmed with your Regional Entity.
Standards and references
- NERC: CIP-005-7 Cyber Security, Electronic Security Perimeter(s)
- NERC: CIP-005-8 redline to last approved (Project 2016-02)
- Federal Register: FERC Order No. 919, Virtualization Reliability Standards
- Texas RE: Standards Upcoming Enforcement Dates, September 2022
- NIST: SP 800-53 Rev. 5 Security and Privacy Controls
- NIST: Cybersecurity Framework 2.0
This guide summarises NERC CIP-005 and is not legal advice. Confirm obligations and effective dates with the standard text and your Regional Entity. Related NHI Mgmt Group resources: NERC CIP Guide · NERC CIP-013 · OT Remote Access Guide · Vendor Privileged Access Management (VPAM) Guide