Join our Newsletter — 33% off our NHI Course
Home› Guides› Reducing Internet-Exposed OT Guide: Finding and Removing Public-Facing…
Guide OT & IoT Security

Reducing Internet-Exposed OT Guide: Finding and Removing Public-Facing Controllers and HMIs

PDF for newsletter subscribers · free to read online

← All guides
By NHI Mgmt Group, under the editorial direction of Lalit Choda Updated 27 November 2026 15 min read
On this page

Controllers, HMIs and remote access gateways that answer on the public internet are the cheapest way into an industrial process, and attackers find them with the same scanning services anyone can use. Government advisories since 2023 describe the same pattern again and again: an exposed PLC or VNC session, a default or missing password, then changed setpoints, suppressed alarms and operators locked out. This guide shows OT asset owners and ICS security engineers how to find their own exposed assets, decide what to fix first, remove or broker each exposure under change control, and stop it coming back. It covers only assets you own or operate: never scan or probe devices that belong to someone else.

Key takeaways

  • The target state is zero direct exposure. CISA's Cross-Sector Cybersecurity Performance Goals (CPG 2.X) say no OT assets should be on the public internet unless explicitly required for operation, with every exception documented and given extra protection.
  • Look from the outside and the inside. External scan results show what the internet sees; your asset inventory and firewall, router and cellular gateway configurations explain why. You need both to close the path rather than just the symptom.
  • Fix by consequence, not by count. An HMI that can change a setpoint with no password outranks a read-only historian web page, even if there are fifty of the latter.
  • Every change to a live process is a process change. Removing a port forward or swapping a modem can break telemetry, vendor support or a safety notification. Use management of change, a rollback plan and operations sign-off.
  • Exposure returns after maintenance visits. Integrators, new cellular routers and emergency fixes reopen paths. Continuous external monitoring and inbound alerting on OT protocol ports are the only way to keep the number at zero.

Why exposed OT matters

MITRE ATT&CK for ICS describes this as T0883 Internet Accessible Device: an attacker reaches the industrial environment through a system exposed directly to the internet without adequate protection, often using the device's own remote access functions. No exploit is needed. If the attacker has to exploit a flaw instead, ATT&CK treats that as a separate technique (T0819); if they come in through a VPN or remote desktop service, it is T0822 External Remote Services.

Two advisories show what this looks like in practice:

  • Unitronics PLCs, 2023 to 2024: CISA advisory AA23-335A (first published 1 December 2023, updated 18 December 2024) describes IRGC-affiliated actors using the CyberAv3ngers persona compromising at least 75 Unitronics Vision Series PLCs in the US, at least 34 of them in water and wastewater. The devices were internet-connected with the default password or none. The actors replaced control logic, defaced the HMI screens and changed the remote communication port from the default TCP 20256 to 20257 so operators could not reconnect.
  • Pro-Russia hacktivists and exposed VNC: a joint FBI, CISA and NSA advisory with international partners, published as a supplement to the May 2025 Primary Mitigations fact sheet, describes groups scanning for VNC on TCP 5900 and nearby ports (5901 to 5910), spraying default, weak or missing passwords, then using the HMI to change setpoints, suppress alarms and change credentials. The usual result was loss of view and forced manual operation.

The actors were opportunistic: they found whatever answered. That is why reducing exposure is the first of the five actions in the CISA Primary Mitigations for OT Guide, and why it pays back faster than almost any other OT control. For the wider programme see the OT Security Guide.

Finding your exposure

Start with a scoped list of what you own: public IP ranges and ASNs registered to the organisation, ranges assigned by ISPs to sites, cellular data plans and SIMs in routers and gateways, and any address space used by integrators or managed service providers on your behalf. The hacktivist advisory specifically tells owners to scan their own IP ranges, including those used by third parties. Then combine four sources.

MethodWhat it showsStrengthsBlind spots
Internet scanning search services (CISA lists Shodan, Censys and Thingful, without endorsement)Banners and services seen on your public addresses, often with product and firmware stringsShows what attackers see; historic data reveals intermittent exposureCellular addresses change; results can be days old; only as good as your IP list
CISA Cyber Hygiene vulnerability scanningContinuous scans of public static IPv4 addresses, weekly reports, urgent alerts for risky services and known exploited vulnerabilitiesFree for eligible US government and critical infrastructure organisations; independent viewEligibility limits; static IPv4 only
External attack surface management (EASM) or your own authorised scansLive state of your ranges on OT ports, certificates, login pagesCurrent, schedulable, can follow DNS and certificate clues to forgotten assetsMust be scoped to assets you own; avoid active probing of fragile devices beyond banner level
Inside-out review: asset inventory, firewall NAT rules, router and cellular gateway configs, vendor remote access toolsWhy a device is reachable: port forward, public IP on the device, modem with a public APN, cloud relayFinds the root cause and paths scanners miss (outbound cloud relays, private APNs reachable from carrier networks)Depends on accurate records; unmanaged modems are by definition missing

Search results by the ports and services your OT actually uses. Typical ones are Modbus TCP 502, S7comm 102, EtherNet/IP 44818, DNP3 20000, IEC 60870-5-104 2404, BACnet 47808, OPC UA 4840 and VNC 5900 to 5910, plus HTTP, HTTPS, Telnet and SSH on PLC, drive, gateway and HMI web interfaces. Vendor-specific ports matter too: the Unitronics default was TCP 20256.

  • Walk the sites: remote pump stations, substations, solar and battery sites and building plant rooms are where cellular routers and integrator-installed gateways live. A physical check against the inventory finds modems that no firewall review will.
  • Ask suppliers: the Primary Mitigations fact sheet notes that misconfigurations come from integrators, managed service providers and default product settings. Ask each OT supplier in writing which remote connections they installed, with what addresses and accounts. See the OT Third-Party and Integrator Access Guide.
  • Record each finding as an asset: add it to the OT asset register with site, owner, process function, exposure path and evidence (scan date, screenshot of the banner). The OT Asset Register Template has the fields. See also the OT Asset Visibility Guide.

Prioritising what to fix

CISA's Internet Exposure Reduction Guidance asks four questions of each exposed asset: is it essential for operations, what operational need justifies the exposure, can access be restricted through a VPN or protected with MFA, and is it patched. Add the consequence of misuse and you have a workable priority.

PriorityTypical findingWhyTarget
P1: act nowHMI, VNC or PLC programming port reachable with default, weak or no password; remote programming enabled; anything that can change setpoints, logic or safety settingsMatches the advisories exactly; direct physical consequenceRemove or block within 24 to 72 hours under emergency change; change passwords at the same time
P2: this monthControl-capable interface behind authentication but exposed (vendor web UI, remote desktop to an engineering workstation, OT protocol port with device authentication)Password spraying and known vulnerabilities still applyMove behind brokered remote access with MFA within 30 days
P3: this quarterRead-only or monitoring interfaces: historian dashboards, building management viewing pages, telemetry gateways with no write functionLeaks process data and can be a pivot; lower direct consequenceRemove or broker; publish data through a DMZ replica instead
P4: justify or removeDeliberate exposure with a business case (for example a supplier cloud service) and compensating controls in placeCPG 2.X allows documented exceptionsWritten exception with owner, expiry date and annual review

Within a priority, order by process consequence (safety and environmental first, then production and customer service) and by how easy the device is to misuse. Fix P1 items before the formal risk assessment, not after it. The IEC 62443-3-2 OT Risk Assessment Guide covers the formal method.

Removing and isolating exposed devices

Every fix touches a running process, so treat it as an OT change. CPG 2.Q asks that OT changes align with defined change control and testing. The OT Management of Change for Cyber guide sets out the full process; the steps below are the exposure-specific version.

  1. Confirm ownership and function. Identify the site, process, owner and every user of the connection: operators on call, vendor support, telemetry, alarm paging, data feeds. An unknown connection is often a supplier's support line or a remote alarm path.
  2. Raise the change. Record the exposure, the planned fix, dependencies, the test, a rollback step and the operations approver. For P1 findings use the emergency change route and complete the record afterwards.
  3. Change credentials first or at the same time. If a device was exposed with a default or weak password, assume it was found. Set a unique strong password, and check logic, setpoints, alarm configuration and user accounts against a known good backup before and after.
  4. Close the path at the source. Remove the NAT or port forward, take the public IP off the device, move the cellular router to a private APN or disable inbound on it, turn off remote programming where it is not needed, and block the OT ports inbound at the perimeter by default.
  5. Replace the access, not just remove it. If someone genuinely needs the connection, give them the brokered path described in the next section before you close the old one, so nobody quietly reopens it.
  6. Test in a supervised window. Have operations confirm control, view, alarms, telemetry and vendor access still work. Keep the rollback ready, but roll back to a blocked state with a temporary allowlist, never back to open exposure.
  7. Verify from outside. Rescan the address and the ports from an external vantage point and attach the evidence to the change record.

Where a device cannot be taken off the internet quickly (a remote site with only a cellular link, for example), apply interim controls: source IP allowlisting for known support addresses, a firewall in front of the device that detects brute force (as AA23-335A recommends), changing the default port, view-only accounts for remote users and time-limited windows. These reduce risk; they do not replace removal.

Secure remote access instead

The Primary Mitigations fact sheet asks operators to revisit the risk trade-offs behind each remote connection and, where remote access is essential, to use a private IP network connection and a VPN with a strong password and phishing-resistant MFA, with least privilege by asset and role and dormant accounts disabled.

PatternHow it worksGood forWatch for
VPN into a DMZ jump hostUser authenticates with MFA to a VPN that lands only in an OT DMZ; a hardened jump host then reaches named OT assetsInternal engineers and long-term integratorsFlat VPN pools that reach the whole OT network; shared jump host accounts
Brokered remote access gatewayOutbound-only connector at the site; users authenticate to a broker with MFA and get a session to one asset, often recordedVendors, multi-site estates, per-session approvalThe broker becomes a high-value identity system; protect its admin accounts like PAM
Private network linksPrivate APN, MPLS or leased line between sites and control centre, no public addressingRemote telemetry and SCADA pollingCarrier private networks still need encryption and authentication of the endpoints
Temporary, approved accessAccess enabled only for a ticketed window, by operations, then disabledInfrequent vendor maintenanceWindows that are never closed; log every enable and disable
  • Where identity fits: remote access is an identity problem as much as a network one. Give every person a named account, use the strongest MFA the path supports (CPG 2.H puts phishing-resistant hardware methods first), scope each vendor account to the assets in their contract, and disable accounts that have not been used. Service accounts used by data feeds or monitoring tools need their own credentials, rotation and an owner. See the OT and ICS Identity and Access Guide.

Keeping exposure from returning

ATT&CK mitigation M0930 Network Segmentation includes periodically inventorying internet-accessible devices to spot deviations from what is expected. In practice that means three layers of monitoring.

  • Outside-in, continuously: schedule external scans or EASM alerts on your ranges at least weekly, subscribe to scan service alerts for your IP space, and use CISA Cyber Hygiene reports where eligible. Any new service on an OT port opens a P1 ticket.
  • At the boundary: alert on any inbound session from an internet-routed address to an OT protocol port or OT subnet. ATT&CK's detection analytics for T0883 describe exactly this, with approved vendor paths suppressed. Also alert on firewall rule changes that add NAT or permit rules toward OT zones.
  • Inside the OT network: monitor for unusual logins, unexpected protocols, controller mode or program changes and setpoint deviations, as the hacktivist advisory recommends. The OT Network Security Monitoring Guide covers sensor placement.
  • Through process: add "no new internet exposure" to supplier contracts and site acceptance tests, require change records for any modem or gateway installation, and include exposure checks in every post-maintenance handover. The OT Product Procurement Guide covers asking suppliers for products without default passwords.

Metrics that show it is working

  • Exposed OT services: count of OT assets reachable from the internet, by priority. Target zero for P1 and P2.
  • Time to close: median hours from detection to verified closure for new P1 findings.
  • Reappearance rate: findings that return within 90 days of closure, by site and supplier.
  • Exception health: share of documented exceptions with a current owner and an unexpired review date.
  • Remote access coverage: share of remote OT sessions that go through the approved brokered or VPN path with MFA.
  • Inventory accuracy: share of external findings that were already in the asset register before discovery.

Framework mapping

FrameworkReferenceHow it applies
CISA CPGs1.A, 2.X, 2.W, 2.H, 2.QAsset inventory including OT; no OT on the public internet unless required; no exploitable services exposed; strongest MFA; OT change control
NIST CSF 2.0ID.AM-01, ID.RA-01, PR.AA-05, PR.IR-01, DE.CM-01, GV.SC-07Hardware inventory, vulnerabilities identified, least privilege, protecting networks from unauthorised access, network monitoring, supplier risk
NIST SP 800-53 Rev. 5SC-7, AC-17, IA-2, CM-8, CM-3, RA-5, CA-7Boundary protection, remote access, authentication, component inventory, change control, scanning, continuous monitoring
ISA/IEC 6244362443-3-3, 62443-2-1, 62443-2-4System security requirements and zones and conduits; asset owner programme; service provider requirements
MITRE ATT&CK for ICST0883, T0822, T0886, T0859; M0930, M0935, M0937Internet Accessible Device, External Remote Services, Remote Services, Valid Accounts; segmentation, limiting access over network, traffic filtering
ISO/IEC 27001:2022 Annex A5.9, 8.20, 8.32Inventory of assets, networks security, change management

Common failure patterns

  • Scanning only the corporate ranges: the exposed devices are on site broadband, cellular SIMs and integrator address space that IT never registered.
  • Closing the port but leaving the default password: if the device was exposed, treat its credentials and configuration as compromised and verify logic against a backup.
  • One-off clean-up: exposure count drops to zero after a project, then climbs back within months because nobody monitors it or writes it into supplier contracts.
  • Exceptions with no expiry: a "temporary" exposure approved for commissioning is still open years later.
  • Changing live systems outside change control: a hurried firewall change cuts alarm paging or telemetry and operations reopen the path to restore it.

Practitioner checklist

  • List every public IP range, ISP-assigned address, cellular SIM and third-party range used for your OT.
  • Search those ranges in an internet scanning service and, if eligible, enrol in CISA Cyber Hygiene scanning.
  • Reconcile findings with the OT asset register, firewall NAT rules and gateway configurations; walk remote sites.
  • Rank findings P1 to P4 by control capability, authentication and process consequence.
  • Close P1 findings within 72 hours under emergency change, changing credentials and checking logic against backups.
  • Give every legitimate user a brokered or VPN path with phishing-resistant MFA before closing the old one.
  • Document any remaining exception with owner, compensating controls and expiry date.
  • Alert on inbound internet connections to OT ports and on firewall changes toward OT zones.
  • Rescan weekly and after every maintenance visit; track reappearance by site and supplier.

Standards and references

Related NHI Mgmt Group resources: OT Security Guide · CISA Primary Mitigations for OT Guide · OT Remote Access Guide · OT Network Segmentation, Purdue Model and IEC 62443 Zones and Conduits Guide · Attack Surface Management Guide

PDF for subscribers

Take this guide with you

Every section, table and checklist in one PDF, with links to the sources and related guides. Subscribe to our weekly NHI & AI Identity Journal and we’ll email you a download link.

Free weekly newsletter

Subscribe to the NHI & AI Identity Journal

The latest on NHI and Agentic AI security – articles, research, breaches, news and events every week.

Bonus 33% off our NHI Course when you subscribe.

PDF Downloads for Newsletter Subscribers

Get the guide

Enter your details and we’ll email you a download link.

The full guide is free to read online. The PDF is a thank you for subscribing.

Fill in all fields marked * and tick both boxes to continue.